Rockwell Automation 1606-XLSDNET4_8 DC Power Supply User Manual

Page 3

background image

DeviceNet

®

Series Power Supply Instruction Manual

Technical Data

1606-XLSDNET4

1606-XLSDNET8

Output Voltage

DC 24.1V

±0.2%

DC 24.1V

±0.2%

factory setting

Adjustment Range

min.

fixed

24-24.5V

Output Current

min.

3.8A

8A

Surge Current Capability

min

5.7A

12A

for typ. 200ms

Over-Current Protection

max. 4.15A

9.5A

continuous operation

NEC Power Classification

min.

NEC Class 2

NEC Class 1

Output Ripple

max. 50mVpp

50mVpp

bandwidth: DC to 20MHz

Line Regulation

max

0.1%

0.1%

V

IN

min to V

IN

max

Load Regulation

max

0.3%

0.3%

no-load full-load deviation

Temperature Coefficient

typ.

0.03% / °C

0.03% / °C

Turn-on Time

typ.

100ms

85ms

including an external 7000µF capacitor

Turn-on Delay

typ.

200ms

600ms

time between turn-on and output ok

Turn-on Overshoot

typ.

0mV

0mV

Over-voltage Protection

max. 29Vdc

29Vdc

AC Input Voltage

-

AC 100-240V

-15/+10%

, 50-60Hz

TN, TT and IT mains

AC Input Current

max. 1.1A - 0.5A

2.3A - 1.0A

at 100 - 240Vac

DC Input

-

DC 110 - 300V

-20/+20%

DC 110 - 300V

-20/+25%

Power Factor

typ.

0.99 - 0.91

0.99 - 0.92

at 100 - 230Vac

AC Inrush Current

max. 15A peak, 1A

2

s

6A peak, 1A

2

s

at 100 - 240Vac

Efficiency

typ.

91.9% / 92.4%

92.3% / 92.7%

at 120 / 230Vac

Losses

typ.

8.0W / 7.5W

16.0W – 15.1W

at 120 / 230Vac

Hold-up Time

typ.

43 / 77ms

32 / 32ms

at 120 / 230Vac

Capacitive Loads

-

No limitations

Inductive Loads

-

No limitations

Limited Warranty

-

1 year from date of purchase

Environment

Operational temperature

-25 to +70°C

De-rate above +60°C

Storage temperature

-40 to +85° C

Storage, transport

Humidity

5 to 95% RH

No condensation allowed

Vibration sinusoidal

2g

IEC 60068-2-6

Shock

15g 6ms, 10g 11ms

IEC 60068-2-27

Allowed output current
versus the ambient
temperature

Ambient temperature is
defined 2cm below the unit.

0%

25%

50%

75%

100%

-40°C -20°C

0°C

20°C 40°C

60°C 80°C

Ambient Temperature

Functional Diagram

Dielectric Strength

Type tests and factory tests:
Conducted by the manufacturer.
Do not repeat test in field!
Field test rules:

(1) Use appropriate test equipment which
apply the voltage with a slow ramp!
(2) Connect L and N together as well as all
output poles.
(3) Use only AC test-voltages with 50/60Hz.
The output voltage is floating and has no ohmic
reference to ground.

A

D

C

B

B

N

L

Input

DC-ok

Earth

Output

-

+

A

B

C

D

Type Test

60s

2500Vac

3000Vac

500Vac

500Vac

Factory Test

5s

2500Vac

2500Vac

500Vac

500Vac

+

+

-
-

V

OUT

DC
ok

Output

Over-

Voltage

Protection

PFC

Converter

Input Fuse
Input Filter
Input Rectifier
Inrush Limiter
Transient Filter

Output

Voltage

Regulator

Power

Converter

Output

Filter

DC ok

Relay

Output

Voltage
Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

Over-

load

DC

ok

L

N

8A unit only

Field Test

5s

2000Vac

2000Vac

500Vac

500Vac

Overload Performance

(typical curves)

0V

4V

8V

12V

16V

20V

24V

0A

1A

2A

3A

4A

5A

Output Current

0V

4V

8V

12V

16V

20V

24V

0A

2A

4A

6A

8A

10A

Output Current

Output characteristic 1606-XLSDNET4

Output characteristic 1606-XLSDNET8

Protection

Output

Overload, no-load, short-circuit proof

Degree of protection

IP 20

EN/IEC 60529

Class of protection

I

PE (Ground) connection required!

Degree of pollution

2

EN 50178, not conductive

Over-temperature protection

yes

Output shut-down with automatic restart

Output over-voltage protection

yes

Output shut-down with automatic restart

Over-voltage category

III

EN 50178

Penetration protection

>3.5mm

e.g. screws, small parts …

Internal input fuse Device protection,
not externally accessible

T3.15A
T6.3A

1606-XLSDNET4
1606-XLSDNET8

DC-ok Relay Contact

This feature monitors the output voltage, which is produced by the power supply, and is
independent of a return voltage from a unit which is connected in parallel.
Contact closes as soon as the output voltage reaches the nominal value.
Contact opens as soon as the output voltage dips more than 10%.
Short dips will be extended to a length of 250ms on the relay.
Dips shorter than 1ms will be ignored.
Contact ratings 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load

250ms

90%

V

ADJ

V

ADJ

closed

open

> 1ms

< 1ms

10%

open

closed

V

OUT


Please note:
The DC-ok feature requires that the output voltage reach the nominal (=adjusted) level after
turn-on in order to function to specification. If this level cannot be achieved, the unit will show
an overload condition. The overload signal will disappear as soon as the adjusted voltage is
reached. This is an important to condition to consider particularly, if the load is a battery or
the power supply is used for N+1 redundant systems.

External fuse on input

Choose value according to the steady state input
current, if needed for branch circuit protection.