Rockwell Automation 1606-XLSDNET4_8 DC Power Supply User Manual
Page 3
![background image](/manuals/578602/3/background.png)
DeviceNet
®
Series Power Supply Instruction Manual
Technical Data
1606-XLSDNET4
1606-XLSDNET8
Output Voltage
DC 24.1V
±0.2%
DC 24.1V
±0.2%
factory setting
Adjustment Range
min.
fixed
24-24.5V
Output Current
min.
3.8A
8A
Surge Current Capability
min
5.7A
12A
for typ. 200ms
Over-Current Protection
max. 4.15A
9.5A
continuous operation
NEC Power Classification
min.
NEC Class 2
NEC Class 1
Output Ripple
max. 50mVpp
50mVpp
bandwidth: DC to 20MHz
Line Regulation
max
0.1%
0.1%
V
IN
min to V
IN
max
Load Regulation
max
0.3%
0.3%
no-load full-load deviation
Temperature Coefficient
typ.
0.03% / °C
0.03% / °C
Turn-on Time
typ.
100ms
85ms
including an external 7000µF capacitor
Turn-on Delay
typ.
200ms
600ms
time between turn-on and output ok
Turn-on Overshoot
typ.
0mV
0mV
Over-voltage Protection
max. 29Vdc
29Vdc
AC Input Voltage
-
AC 100-240V
-15/+10%
, 50-60Hz
TN, TT and IT mains
AC Input Current
max. 1.1A - 0.5A
2.3A - 1.0A
at 100 - 240Vac
DC Input
-
DC 110 - 300V
-20/+20%
DC 110 - 300V
-20/+25%
Power Factor
typ.
0.99 - 0.91
0.99 - 0.92
at 100 - 230Vac
AC Inrush Current
max. 15A peak, 1A
2
s
6A peak, 1A
2
s
at 100 - 240Vac
Efficiency
typ.
91.9% / 92.4%
92.3% / 92.7%
at 120 / 230Vac
Losses
typ.
8.0W / 7.5W
16.0W – 15.1W
at 120 / 230Vac
Hold-up Time
typ.
43 / 77ms
32 / 32ms
at 120 / 230Vac
Capacitive Loads
-
No limitations
Inductive Loads
-
No limitations
Limited Warranty
-
1 year from date of purchase
Environment
Operational temperature
-25 to +70°C
De-rate above +60°C
Storage temperature
-40 to +85° C
Storage, transport
Humidity
5 to 95% RH
No condensation allowed
Vibration sinusoidal
2g
IEC 60068-2-6
Shock
15g 6ms, 10g 11ms
IEC 60068-2-27
Allowed output current
versus the ambient
temperature
Ambient temperature is
defined 2cm below the unit.
0%
25%
50%
75%
100%
-40°C -20°C
0°C
20°C 40°C
60°C 80°C
Ambient Temperature
Functional Diagram
Dielectric Strength
Type tests and factory tests:
Conducted by the manufacturer.
Do not repeat test in field!
Field test rules:
(1) Use appropriate test equipment which
apply the voltage with a slow ramp!
(2) Connect L and N together as well as all
output poles.
(3) Use only AC test-voltages with 50/60Hz.
The output voltage is floating and has no ohmic
reference to ground.
A
D
C
B
B
N
L
Input
DC-ok
Earth
Output
-
+
A
B
C
D
Type Test
60s
2500Vac
3000Vac
500Vac
500Vac
Factory Test
5s
2500Vac
2500Vac
500Vac
500Vac
+
+
-
-
V
OUT
DC
ok
Output
Over-
Voltage
Protection
PFC
Converter
Input Fuse
Input Filter
Input Rectifier
Inrush Limiter
Transient Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Over-
load
DC
ok
L
N
8A unit only
Field Test
5s
2000Vac
2000Vac
500Vac
500Vac
Overload Performance
(typical curves)
0V
4V
8V
12V
16V
20V
24V
0A
1A
2A
3A
4A
5A
Output Current
0V
4V
8V
12V
16V
20V
24V
0A
2A
4A
6A
8A
10A
Output Current
Output characteristic 1606-XLSDNET4
Output characteristic 1606-XLSDNET8
Protection
Output
Overload, no-load, short-circuit proof
Degree of protection
IP 20
EN/IEC 60529
Class of protection
I
PE (Ground) connection required!
Degree of pollution
2
EN 50178, not conductive
Over-temperature protection
yes
Output shut-down with automatic restart
Output over-voltage protection
yes
Output shut-down with automatic restart
Over-voltage category
III
EN 50178
Penetration protection
>3.5mm
e.g. screws, small parts …
Internal input fuse Device protection,
not externally accessible
T3.15A
T6.3A
1606-XLSDNET4
1606-XLSDNET8
DC-ok Relay Contact
This feature monitors the output voltage, which is produced by the power supply, and is
independent of a return voltage from a unit which is connected in parallel.
Contact closes as soon as the output voltage reaches the nominal value.
Contact opens as soon as the output voltage dips more than 10%.
Short dips will be extended to a length of 250ms on the relay.
Dips shorter than 1ms will be ignored.
Contact ratings 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
250ms
90%
V
ADJ
V
ADJ
closed
open
> 1ms
< 1ms
10%
open
closed
V
OUT
Please note:
The DC-ok feature requires that the output voltage reach the nominal (=adjusted) level after
turn-on in order to function to specification. If this level cannot be achieved, the unit will show
an overload condition. The overload signal will disappear as soon as the adjusted voltage is
reached. This is an important to condition to consider particularly, if the load is a battery or
the power supply is used for N+1 redundant systems.
External fuse on input
Choose value according to the steady state input
current, if needed for branch circuit protection.