Typical wiring to a controller is shown in the diagram. For 4…20 mA loop signal, only
the PWR and OUT terminals are used.

Field Calibration

The unit can be calibrated in the field by using precision resistor values equal to the zero and
span of the transmitter temperature range.

1. Disconnect the sensor from the transmitter and connect the resistor that represents the

zero value to the EXC and NEG terminals.

2. Adjust the ZERO pot until the desired output is achieved.
3. Connect the resistor that represents the span value to the EXC and NEG terminals.
4. Adjust the SPAN pot until the desired output is achieved.

Repeat these steps until no further adjustment is required.

TIP

If the unit uses a three-wire sensor, a jumper must be placed between EXC and
SEN.

NEG

EXC

SEN

PW

R

CO

M

OU

T

SPAN

ZERO

+ 24V DC -

ANL IN 0 +

ANL IN 0 -

Analog Current Input

ANL COM

Loop Power Supply

2-wire RTD

Sensor

Temperature Transmitter