Iv. conversion module specifications, Iii. compatibility – Rockwell Automation 1492-CM1771-LD008F Fused Field Conversion Module User Manual
Page 3
![background image](/manuals/578551/3/background.png)
(3)
IV. Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
Specification
Dimensions
Approximate Shipping Weight
Storage Temperature
-40 to +85°C (-40 to +185°F)
Operating Temperature
0 to 60°C (32 to 140°F)
Operating Humidity
5 to 95% at 60°C (non-condensing)
Shock
Non
-
operating
Operating
50g
30g
Operating Vibration
2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)
Maximum Operating Voltage
60 Vdc
Max. Module Operating Current
Per Point:
Per Module:
2 Amps
8 Amps
Agency Certifications
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Pollution Degree
2
Environmental Rating
IP20
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
NOTICE
Value
Fusing
One, 10 Amps (maximum current based on conversion components)
III. Compatibility
1771
Digital I/O Module
1756
Digital I/O Module
1492
Conversion Module
1492
Cable
1771-OBD 1756-OC8
(Qty
2)
1492-CM1771-LD008F
1492-CONCAB005S1
Foot Notes:
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific 1771
and 1756 I/O modules involved. The (2) 1756 modules must be located directly next to each other in the 1756
chassis.
The 3 numbers indicate the cable length of the 1492 Cable. Recommended cable length of 0.5M is shown.
Alternative cable lengths are as follows:
1.0M = 1492-CONCAB010S1
The "F" at the end of the 1492 I/O Conversion Module Catalog Number indicates it is fused to match the functionality
of the 1771 module being replaced.
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
265.4 g (0.58 lbs) (includes carton)
PN-114280
DIR 10000060091 (Version 01)
Publication 1492-IN038B-EN-E