Rockwell Automation 1195C-LK1_LK2_LK3 200A / 400A / 600A Vacuum Contactor Lug Kits User Manual
Bulletin 1102c vacuum contactor lug kits, E - doc
ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.
42052-097
G. Ushakow
N/A
N/A
N/A
42052
1006490
1
INSTRUCTION SHEET
BULLETIN 1102C 200A/400A/600A VACUUM CONTACTOR
LUG INSTALLATION
2-24-04
Mark Jutz
2-24-04
D. Josef
2-24-04
1
2
42052-104
REVISION
AUTHORIZATION
DIMENSIONS APPLY BEFORE
SURFACE TREATMENT
H
A
B
C
D
E
F
G
(DIMENSIONS IN INCHES)
TOLERANCES UNLESS
OTHERWISE SPECIFIED
REFERENCE
SHEET
OF
DWG.
B
DR.
CHKD.
APPD.
DATE
DATE
DATE
±
±
±
ANGLES:
.XXX:
.XX:
THIS DRAWING IS THE PROPERTY OF
THE ALLEN-BRADLEY CO. INC.
AND MAY NOT BE COPIED, USED OR
DISCLOSED FOR ANY PURPOSE EXCEPT
AS AUTHORIZED IN WRITING BY
THE ALLEN-BRADLEY CO. INC.
LOCATION : MILWAUKEE,
WISCONSIN
U.S.A.
SIZE
1
2
3
4
5
6
7
8
E - DOC
Bulletin 1102C Vacuum Contactor Lug Kits
(Cat 1195C-LK1, -LK2, -LK3)
Lug Installation (Cat 1195C-LK1)--Wire Range: #2/0 - 250 MCM
Vacuum Contactor - 200A
Lug Installation (Cat 1195C-LK2)--Wire Range: (2) #6 - 300 MCM
Vacuum Contactor - 400A
VAC
UUM
CON
TAC
TOR
VAC
UUM
CON
TAC
TOR
VAC
UUM
CON
TAC
TOR
1
2
3
VACU
UM C
ONTA
CTO
R
VA
CU
UM
CO
NTA
CTO
R
180 - 210 lb-in
3/8-16 x 1-1/2" Bolt
Trim end of Boot to
slide over conductor
prior to installing Lug
5/16-18 x 3/4 Bolt
5/16 Lock Washer
5/16 Flat Washer
Boot
(shown installed over
center phase Lug)
3/8 Flat Washer
1. Remove existing 5/16 hardware.
2. Trim end of boot and slide over center phase conductor.
3. Assemble lugs to power terminals using hardware supplied in kit. Torque screws to 125 - 145 lb-inches.
4. Connect conductors. Torque lug set screws to 275 lb-inches.
275 lb-in
Lug
275 lb-in
125 - 145 lb-in
3/8-16 Nut
3/8 Lock Washer
3/8 Flat Washer
5/16" Allen Wrench
Anti-Rotation Clip
Lug
5/16" Allen Wrench