beautypg.com

Installation – Rockwell Automation 1397 150HP AC Line Disconnect Inst. User Manual

Page 2

background image

1397 150HP AC Line Disconnect

2

1397-5.21 July, 1997

GRD

A1

45

P4
P4
P4

S4

S4

S4

181

182

183

Retaining

Screw

Panel

Tab

Panel

Tab

Retaining

Screw

2

Loosen the (2) auxiliary panel cover retaining screws. To lift out
the auxiliary panel, loosen the screws only enough to allow the
panel tabs to slide out.

1

Remove and lockout all incoming power to the drive. Disconnect
the incoming power lines from the drive by removing the wire
binding screws on the box connectors at terminals 181, 182

&

183.

Installation

ATTENTION:

Electric Shock can cause injury or death.

Remove all power before working on this product.

The drive is at line voltage when connected to incoming AC
power. Before proceeding with any installation or
troubleshooting activity, disconnect lockout and tag all
incoming power to the drive. Verify with a voltmeter than no
voltage exists at terminals L1, L2 and L3 on the drive input
power terminal block.

!