Rockwell Automation 1609-PSB1 Uninterruptible Power Supply Service Bypass Switch User Manual
Rockwell Automation Equipment
1609-PSB1
Service Bypass Switch
Entire contents copyright © 2006 by Rockwell Automation corporation. All rights
reserved. Reproduction in whole or in part without permission is prohibited.
A-B and Allen-Bradley are registered trademarks of Rockwell Automation Corporation.
All other trademarks are the property of their respective owners.
90-007 rev 1
Note: Read the safety information sheet before installation.
Illustrations in this document may differ slightly from the actual hardware.
Attention: This product is for use in a controlled environment. Refer to product
specifications for environmental limits.
R
ACK
M
OUNTING
n
o
Set SBP in the rack. If hardwiring is required, see Connecting Power
section before screwing into the rack.
n
W
ALL
M
OUNTING
41063-300-01(1)
o
Whenever possible, attach one top screw and one bottom screw into a wall stud. If stud
mounting is not possible, use an expandable wall anchor. Screws are not included; .25” x
2” lag bolts are recommended.
T
OWER
O
PTION
n
Remove screw from the top and bottom rear of both the UPS and SBP. Install tie
brackets and reattach screws.
o
Unscrew and remove top cover of the
UPS.
p
Attach bracket to top of UPS and SBP.
q
Reattach top cover of the UPS.
Note: The 1609-SBP1, when used in conjunction with an 1609-P3000A or 1609-P5000E UPS in a tower
configuration without an external battery pack 1609-PXBP, is suitable for mounting on concrete or other
non-combustible smooth surfaces only.
41063-300-01(1)
U
SER
C
ONFIGURABLE
Attention: When using an online UPS, put the UPS in automatic bypass mode before
rotating the SBP switch.
1. Normal: Power is directed from the utility outlet, through the Bypass Panel and UPS,
and to connected equipment. For use during normal UPS operation.
2. Test: Power supplied to the UPS is not output. Use when tests are being conducted on
the UPS, and connected equipment is not yet desired.
3. Bypass: Power from the utility outlet is filtered through the Bypass Panel, and to the
connected equipment. Use to bypass the UPS, when functioning improperly.
Note: While operating in ‘Test’ or ‘Bypass’ mode, power to the connected equipment is
not conditioned by the UPS. At this time, the “Equipment Protection Policy” is not valid.
I
DENTIFYING THE
P
ANEL
Service Bypass Panels will differ. Refer to chart for unit specifications.
Note: HW= Hardwire
Service Bypass
Panel
Corresponding
UPS Systems
Bypass
Input
UPS
Input
UPS
Output
PDU
Panel
1609-PS
B
1
1609-P3000A
1609-P3000H
1609-P5000E
1609-P8000E
1609-P10000E
HW (1Ph)
HW (1Ph)
HW
HW
*
For loads exceeding 3kVA, hardwiring is necessary.
41063-300-01(1)
x4
x4
x4
x8
Rear
Front
x1
x4
x8
x2
x2
x2