Rockwell Automation 1492-CM800-LA004 Field Wire Conv. Module for Modicon B872-200 to 1756-OF6VI User Manual
Page 3

(3)
10000021843
(Version 00)
V. 1492-CM800-LA004 Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
Specification
Value
Dimensions
288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)
11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width)
Approximate Shipping Weight
300g (0.66 lbs) (includes carton)
Storage Temperature
-40 to +85°C (-40 to +185°F)
Operating Temperature
0 to 55°C (32 to 131°F)
Operating Humidity
5 to 95% at 55°C (non-condensing)
Shock
Non-operating
Operating
50g
30g
Operating Vibration
2g @ 10-500Hz
Maximum Operating Voltage
60 Vdc
Max. Module Operating Current
Per Point:
Per Module:
2 Amps (1492-CABLE connection pins are limited to 2A per pin)
12 Amps
Agency Certifications
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Pollution Degree
2
Environmental Rating
IP20
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
NOTICE
6
14
12
26
24
34
32
20
21
22
23
27
28
+
-
4
Analog Output 1
Analog Common 1
5
13
25
3
9
10
15
16
18
19
7
33
8
11
17
29
30
31
35
36
37
38
1
2
39
Not Used
Not Used
Frame Ground
Frame Ground
Analog Common 1
13
25
24
23
22
21
19
18
17
16
15
14
SH
12
11
9
6
4
2
20
1
OUT-0
RTN-0
5
OUT-1
2
RTN-1
6
OUT-2
7
RTN-2
11
OUT-3
8
RTN-3
12
RTN-4
19
OUT-4
15
Not Used
14
Not Used
10
Red
Black
White
Black
Green
Black
Blue
Black
RTN-5
20
OUT-5
16
Yellow
Black
Brown
Black
Orange
Black
Analog Output 2
Analog Common 2
Analog Common 2
Analog Output 3
Analog Common 3
Analog Common 3
Analog Output 4
Analog Common 4
Analog Common 4
40
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Frame Ground
Frame Ground
1492-CM800-LA004 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out
to any device in the control cabinet where the conversion is to be performed. Ensure work is performed
by qualified personnel.
WARNING