Rockwell Automation 1494V-DS600 - Series D Variable Depth 600A Disconnect Switch User Manual
Page 2

PN-133643
DIR 42052-184 (Version 03)
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
ATTENTION: Check for proper operation.
Go to Installation Instruction Sheet 42052-183-01.
Trailer Fuse Block Installation
5
3
Connecting Rod Installation
4
Cutting Connecting Rod
(Cut (2) Connecting Rods; first rod connects the handle to the switch, second rod provides
stiffening for the enclosure flange)
Measure working depth of enclosure.
Measure, mark and
cut (2) connecting rods.
1
2
Remove burrs.
3
N minus 3-3/4"
First rod connects the handle to the switch
Second rod provides stiffening for the enclosure flange
N
Enclosure
Working Depth
(Inside Flange
of Enclosure to
Mounting Plate)
Mounting
Plate
Drive Bar
2
Rotate connecting rod into
drive bar 15 turns.
O
P
E
N
4
3
Pull rod up and verify if
rod is 1/2" away from
touching bottom of
spring bracket. (If not,
rotate rod accordingly)
1/2"
Clearance
Connecting
Rod
Hitch Pin
Primary Link
5
6
8
7
Verify that disconnect switch and handle are in "OFF"
position. (Switch blades will show “OPEN”)
1
9
10
11
150 - 200 lb-in
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1494V-IN103C-EN-E - January 2013