Front panel, Display mode and error messages – Rockwell Automation 937CU-AISTR-DC1 Strain Gauge Converter Installation Instructions User Manual
Page 9
7
Bul. 937
C Strain Gauge Converter Installation Instructions
Front panel
On the front panel of the Strain Gauge Converters you will find:
• LED ERR (red) to indicate
− a sensor fault (flashes red)
− the simulation mode (only when using FDT flashes red)− a
device fault (steady red)
• PWR LED (green), to indicate the presence of the supply voltage
• LED OUT 1 (yellow), to indicate that relay 1 is active
• LED OUT 2 (yellow), to indicate that relay 2 is active
• serial RS 232 interface to connect to a PC for parameterisation and
diagnosis of the Strain Gauge Converter using
FDT.
• a display for measured value and error message display and for
display during parameterisation mode
• four buttons for parameterisation of the Strain Gauge Converters
− S (Up)
− T (Down)
− ESC (Escape)
− OK
Display mode and error messages
Measured value display
• In normal operation, the current net value is indicated on the display in the selected unit.
• If you hold down the T key, the current gross value is indicated on the display in the selected unit.
• If you hold down the S key, the mV value actually measured by the Strain Gauge Converters on
the terminals 1 and 2 is indicated on the display.
• As usual, the following applies: net value = gross value - tare