background image

599-GR4 (Disconnect Sizes 30A - 60A)

Enclosure Mounting Holes for Accessory Ground Kit
1. Holes are pre-punched for #10-32 thread cutting screws.

2. Holes are 2-7/16 inches apart.
3. Accessory mounting orientation will either be vertical or horizontal. Mounting depends on enclosure type and size.

599-GR5 (Disconnect Sizes 100A - 200A)

Service Disconnect Ground Kit Installation Instructions for
Bulletin 1494H (Heavy Duty) and Bulletin 1494HL (General Duty) Safety Switches

(Cat 599-GR4, -GR5)

42052-165 (Version 02)

Printed in U.S.A.

1

2

15 - 20 lb-in

41 - 45 lb-in

#6 - #4

32 - 35 lb-in

#14 - #10

36 - 40 lb-in

#8

Small Holes
60

o

or 75

o

C

#14 - #8 CU
#12 - #8 AL

15 - 20 lb-in

2

Large Holes

60

o

or 75

o

C

#14 - #4 CU

#6 - #4 AL

60

o

or 75

o

C

#12 - 1/0 CU / AL

120 lb-in

3/16" Hex

WARNING

To prevent electrical shock, disconnect from power source before installing or servicing.