Rockwell Automation 500F-xOD930 Contactor Installation User Manual
Bulletin 500f contactor installation, Short circuit current ratings
Bulletin 500F Contactor Installation
(Cat 500F-AOD930; 500F-BOD930; 500F-COD930; 500F-DOD930; 500F-EOD930)
Short Circuit Current Ratings
PN-68120
DIR 10000093749
(Version 02)
Printed in U.S.A.
To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free
from contaminants.
Avant le montage et la mise en service, couper l'alimentation secteur pour éviter toute décharge. Prévoir une mise en coffret ou
armoire appropriée. Protéger le produit contre les environnements agressifs.
Desconéctese de la corriente eléctrica, antes de la instalación o del servicio, a fin de impedir sacudidas eléctricas. Instálelo en una
caja apropiada. Manténgalo libre de contaminantes.
NOTE: For NEMA Sizes 0, 1 and 2, if space is critical, the overload relay mounting plate can be detached from the
contactor mounting plate by removing the (2) #8-32 screws.
WARNING
AVERTISSEMENT
WARNUNG
35 lb-in
Size 2
140 lb-in
Size 3
200 lb-in
Size 4
Standard Fault Short Circuit Ratings
Contactor/Starter
(notes a & b)
NEMA
Sizes
Max. Voltage (V)
SCCR
(kA)
500-**/500F-**/509-**
0,1,2 & 3
240 1Ш, 600 3Ш
5
500-E*/500F-E*/509-E*
4
600 3Ø
10
Contactors and Starters Protected by Inverse-Time Circuit Breakers
Contactor/Starter
(note b)
NEMA
Size
Max.
Voltage (V)
(3Ø unless
noted)
Max. A-B Bul.
140U Circuit
Breaker (note c)
(Starters Only)
SCCR
(kA)
Max. Cutler-Hammer
FDB/LFD Circuit
Breaker / Current
Limiter Combination
SCCR (kA)
240
140U-H_C3-C40
25
FDB 3025/LFD 3070R
100
(1Ø & 3Ø)
480
140U-H_C3-C40
25
FDB 3025/LFD 3070R
100
600
140U-H_C3-C20
18
240
140U-H_C3-C40
25
FDB 3050/LFD 3070R
100
(1Ø & 3Ø)
480
140U-H_C3-C40
25
FDB 3035/LFD 3070R
100
600
140U-H_C3-C20
18
480
140U-H_C3-C70
25
FDB 3100/LFD 3150R
100
(240V Max)
600
140U-H_C3-C50
18
240
140U-H_C3-D12
25
FDB 3150/LFD 3150R
100
480
140U-H_C3-D12
25
FDB 3125/LFD 3150R
100
600
140U-H_C3-D10
18
FDB 3100/LFD 3150R
100
480
140U-H_C3-D12
25
FDB 3150/LFD 3150R
100
600
140U-H_C3-D12
18
FDB 3150/LFD 3150R
100
480
140U-J_D3-D20
25
600
140U-J_D3-D17
18
500-E*/500F-E*/509-E*
4
500-E*/500F-E*/509-E*
4
500-A*/500F-A*/509-A*
0
(note d)
500-B*/500F-B*/509-B*
500-D*/500F-D*/509-D*
3
1
500-C*/500F-C*/509-C*
2
High Fault Short Circuit Ratings
Contactors and Starters Protected by Fuses
Class R
Class J
240 1Ø & 3Ш
30
30
100
600
30
30
100
240 1Ш & 3Ш
60
100
100
600
30
50
100
240 1Ш & 3Ø
100
200
100
600
60
100
100
240
200
350
100
600
100
200
100
240
300
500
100
600
200
400
100
500-E*/500F-E*/509-E*
4
500-C*/500F-C*/509-C*
2
500-D*/500F-D*/509-D*
3
SCCR
(kA)
500-A*/500F-A*/509-A*
0
500-B*/500F-B*/509-B*
1
Contactor/Starter
(note b)
NEMA
Size
Max. Voltage (V)
(3Ø unless noted)
Max. Fuse Rating
High Fault Short Circuit Ratings
Contactors and Starters Protected by Instantaneous-Trip Circuit Breakers
Contactor/Starter
(note b)
NEMA
Size
Max.
Voltage (V)
(3Ø unless
noted)
Max. A-B Bul.
140M Circuit
Breaker
SCCR
(kA)
480
140M-I8P-C15
42
600
140M-I8P-C15
25
480
140M-I8P-C30
42
600
140M-I8P-C30
25
240
140M-I8P-D10
42
480
140M-I8P-C50
42
600
140M-I8P-C50
25
240
140M-I8P-D15
65
480
140M-I8P-D10
65
600
140M-I8P-D10
25
480
140M-I8P-D15
65
600
140M-I8P-D15
25
500-A*/500F-A*/509-A*
500-B*/500F-B*/509-B*
500-C*/500F-C*/509-C*
500-D*/500F-D*/509-D*
500-E*/500F-E*/509-E*
4
0
3
2
1
Specific Notes from SCCR Tables
c) Number after "H" or "J" can be 2, 3, 6 or 1
General Notes for Short Circuit Current Rating (SCCR) Information
1) The ratings shown are in accordance with UL 508 and CSA 22.2 No. 14
4) The SCCR values listed are kA (1000's amperes) RMS symmetrical
2) The devices and ratings shown are those most commonly needed;
additional ratings may be available
3) Additional limitations may apply. Refer to applicable national and local
electrical codes
b) * Includes all contactor variations following the Size letter, and starter
variations with eutectic or E1 Plus overload relays (except .2 - 1 FLA range)
a) ** Includes suffixes A*, B*, C* & D*. Refer to note b.
d) For Size 0, combinations with 140U-* circuit breakers include starters with
eutectic overloads (not E1 Plus)
Tightening Torque lb-in (N
s
M)
Catalog
Nu
Mber
For all Catalog Nu
Mbers:
Control Connections Wire Range: AWG 18 -12
Control Connections Tightening Torque: 12 lb-in (1.4 N
s
M)
Power Wires and Tightening Torques
NOTE: Use 60° / 75° C Copper Wire Only.
Contactor
NEMA Size
Wire
Range
(AWG)
Lug to
Ter
Minal
Wire in
Lug
Overload Relay
to Contactor
500F-
AOD930
14 – 4
2
500F-
BOD930
500F-
COD930
35 (4.0)
45 (5.1)
35 (4.0)
500F-
DOD930
150 (17.0)
140 (15.8)
500F-
EOD930
14 – 8
0
-
20 (2.3)
23 (2.3)
1
20 (2.3)
23 (2.3)
14 – 8
-
3
140 (15.8)
8 – 1/0
4
200 (22.6)
275 (31.1)
200 (22.6)
6 – 4/0