Caution – Rockwell Automation 140U Instructions for Padlockable Handle Lock Hasp Installation User Manual
Page 2
Page
2
Figure 2- 1 Padlockable Handle Lock Hasp Installation
SPECIAL ATTENTlON SHOULD BE PAID TO
REVERSE FEED APPLICATIONS TO ENSURE NO
VOLTAGE IS PRESENT. THE VOLTAGES IN ENER-
GIZED EQUIPMENT CAN CAUSE DEATH OR
SEVERE PERSONAL INJURY.
Note:
When the padlockable handle lock hasp is
mounted on the circuit breaker cover, part of the
nameplate information is covered. Before mounting
the hasp, make sure that the information is recorded
for future reference. A blank nameplate is supplied
to record hidden information. The nameplate
should be placed on the side of the circuit breaker
or another convenient location adjacent to the cir-
cuit breaker.
The following steps describe how to mount the pad-
lockable handle lock hasp in the left-pole position
of the circuit breaker. The same procedure is used
for mounting the hasp in the right pole position.
2-1.
Mounting holes are located in the cover under the
nameplate. Find the mounting holes using the
locating marks in the nameplate. (See Fig.
2-1 .)
2-2...
Using a pencil or similar pointed tool, punch
through the area of the nameplate covering holes
2
and 3
(4
and
5
for right hand mounting).
2-3.
For mounting over the left pole, letter L on
mounting plate must be toward the line end of the
circuit breaker (Fig. 2-2). For mounting over the
right pole, letter R
must be toward the line end of the
circuit breaker.
2-4.
Position mounting plate on cover. Align mounting
holes. (See Fig. 2-2).
CAUTION
FIRMLY TIGHTEN, BUT DO NOT OVERTIGHTEN,
MOUNTING PLATE SCREWS. OVERTIGHTENING
SCREWS CAN DAMAGE THE CIRCUIT BREAKER
COVER. USE ONLY HARDWARE PROVIDED, DO
NOT SUBSTITUTE.
2-5.
Secure mounting plate with two special
#10 (4.8
mm)
crossrecessed head, thread-cutting screws
provided. Torque screws to
30
Ib.-in.
(3.5
Nm).
Do not substitute hardware.
2-6.
Move circuit breaker handle to the OFF position.
Hinge lockplate over staple. Check that padlock
shackle fits through staple and that tab on lock
plate blocks path of circuit breaker handle.
2-7.
Remove padlock. Hinge lockplate away from
circuit breaker handle. Move circuit breaker
handle to the
ON
position. Hinge lockplate over
shackle and check that tab blocks path of circuit
breaker handle. (Lock On/Off Styles Only)
Mounting
Plate
Lockplate
Mounting
Plate
Securing
Screws
Staple
Figure 2-2 Mounting Hole Locations
40752-092 (1)
Effective 05/02
Printed in U.S.A. /TQC