Bulletin 599 Service Disconnect Ground Kit Installation Instructions
INSTALLATION FOR 599-GR1 AND 599-GR2:
NOTE:
Use 599-GR1 for starter sizes 0-2 and disconnect sizes 30A-60A.
Use 599-GR2 for starter sizes 3-4 and disconnect sizes 100A-200A.
Use 599-GR3 for starter sizes 5-6 and disconnect sizes 400A-600A.
(Cat. No. 599-GR1, -GR2, -GR3)
A T T E NT I ON: T o prevent electrical shock, disconnect from power source before installing or
servicing. Install in suitable enclosure. K eep free from contaminants.
1
2
1
77-01-1
2
1000790
42052-031
OF
N/A
N/A
N/A
REVISION
AUTHORIZATION
DR.
CHKD.
APPD.
DATE
DATE
DATE
E - DOC
LOCATION: MILWAUKEE, WISCONSIN U.S.A.
B-vertical.ai
DWG.
SIZE
SHEET
B
1
2
3
4
5
6
7
8
A
B
C
D
E
F
G
H
REFERENCE
DIMENSIONS APPLY BEFORE
SURFACE TREATMENT
(DIMENSIONS IN INCHES)
TOLERANCES UNLESS
OTHERWISE SPECIFIED
.XX:
.XXX:
ANGLES:
42052
THIS DRAWING IS THE PROPERTY OF
ROCKWELL INTERNATIONAL CORPORATION
OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,
USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY
ROCKWELL INTERNATIONAL CORPORATION
BULLETIN 599 SERVICE DISCONNECT
GROUNDING KIT INSTALLATION INSTRUCTIONS
C. KACZYNSKI
4-27-01
9-23-02
9-23-02
M. JUTZ
J. KOZICZKOWSKI
Locate ground stud (1) in the lower left corner of enclosure base.
1.
Stack lugs (2) over ground stud.
2.
Install and tighten locknut (3) to torque of
40-60 LB.-INS. (4.5-6.8 N·M)