Installation - 100-c contactor to coil module, Short circuit ratings, 3e300 sensing module – Rockwell Automation 592-ESM-xxx-xxx E300 / E200 Sensing Module User Manual
Page 3

Installation - 100-C Contactor to Coil Module
3
E300 Sensing Module
Publication 193-IN057E-EN-P - June 2014 PN-248343 DIR 10000518533 (Version 04)
193-EIO-CM-_ _ _
A2
PE
A1
A1
A1
R03
R04
A2
(+)
(-)
Relay 0
A1
100-C Contactor
A2
7 -11 lb-in
9 - 22 lb-in
5 - 7 lb-in
Table 1 Standard Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1
600
Overload Relay using
Sensing Module
Catalog Number
Max. Available Fault
Current (A)
Maximum Voltage (V)
Short Circuit Ratings
The E300 / E200 overload relay is suitable for use on circuits capable of delivering not more than the RMS symmetrical amperes listed in the following tables:
5,000
193-ESM-___-30A-C23,
193-ESM-___-30A-C55,
193-ESM-___-60A-C55,
193-ESM-___-30A-E3T,
193-ESM-___-60A-E3T,
592-ESM-___-30A-S2,
592-ESM-___-60A-S2,
Table 2 Short Circuit Ratings per EN60947-4-1
Overload Relay using
Sensing Module
Catalog Number
Maximum Voltage (V)
Prospective Short Circuit
Current,
Ir (A)
Conditional Short Circuit
Current,
Iq (A)
193-ESM-___-30A-C23,
193-ESM-___-30A-C55,
193-ESM-___-30A-E3T,
592-ESM-___-30A-S2,
193-ESM-___-60A-C55,
193-ESM-___-60A-E3T,
592-ESM-___-60A-S2,
3,000
100,000
690
Sensing Module
Catalog Number
Contactor Catalog Number
Max. Starter FLC (A)
Max. Available Fault
Current (A)
Maximum Voltage (V)
Class J or CC Fuse
(A)
9
20
12
20
16
30
23
30
30
50
37
50
43
70
55
80
100,000
600
Table 3 High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 100-C and 100-D, IEC, contactors protected by fuses
193-ESM-__-30A-C55,
193-ESM-__-60A-C55
193-ESM-__-30A-C23
100-C09
100-C12
100-C16
100-C23
100-C30
100-C37
100-C43
100-C55
Replacement Contactor
Coil Modules
Contactor
193-EIO-CM-C23
193-EIO-CM-C55
100-C09 . . . 100-C23
100-C30 . . . 100-C55
1
2
5
4
6
IN1
IN0
A2
A1
R04
R03
3
193-ESM-___-30A-T,
193-ESM-___-60A-T
193-ESM-___-30A-T,
193-ESM-___-60A-T