Rockwell Automation 440P-WA1A Lever Arms User Manual
Rockwell Automation Equipment
Installation and Operating Instructions
Bulletin 440P-WA1 & 440P-WA1A Lever Arms
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.
This publication does not include all specifications, dimensions, or any special installation considerations.
Refer to the product catalog pages for additional information.
General Data
• Designed for 440P-A short lever arm limit switches
• Metal or nylon roller available
• Roller diameter 13.5 mm (0.53 in.) x width 5.2 mm (0.2 in.)
• Lever arm radius 25 mm (0.98 in.)
• Lever arm length 40 mm (1.57 in.)
• Includes lock nut and washer
Principles, Standards, and Implementation
Operating specifications must be followed. Actuators should
be displaced beyond the point where direct opening action
occurs. If adjustable actuators become loose they may defeat
the direct opening action feature of the limit switch. These
devices are not to be used to directly control a motor.
ATTENTION: To avoid electrical shock and unintended
operation of equipment, disconnect all
power to the limit switch and the controlled
equipment before proceeding with any
repair or adjustment of the limit switch.
IMPORTANT: Installation of Allen-Bradley limit switches should be in
accordance with local and/or national codes. Servicing
energized industrial control equipment can be hazarous if
not in accordance to recommended safety procedures.
Lever arm with nylon roller
shown installed
Lever Arm Dimensions [mm (in.)]
Instructions
1. Mount lever arm on keyed shaft in desired position.
2. Install washer.
3. Install Hex lock nut.
4. Torque Hex lock nut to 1…1.4 N•m (8.85…12.39 lb•in).
ATTENTION: For safety applications
Rockwell Automation recommends
replacing the complete limit switch.
11.1 (0.44)
6.3
(0.25)
15.3 (0.6)
2 (0.08)
Ш7 (0.28)
Ш13.5 (0.53)x5.2 (0.2)
Metal/Nylon Roller
R8
6
(0.24)
25 (0.98)