Table A Response PDU

Table B Error PDU

Examples

Writing Drive Parameters

Write Parameters 38 through 40

• Parameter P038 [Speed Reference] = 3, “4-20mA Input”
• Parameter P039 [Accel Time 1] = 5.0 Sec
• Parameter P040 [Decel Time 1] = 15.0 Sec

Writing Control Registers

In the PowerFlex 40 drive the logic command can be accessed at address
0x2000 and the frequency reference can be accessed at address 0x2001.
These addresses can be written sequentially using Modbus function 16
(0x10). To set the following values:

• Logic Command = 0x1234
• RS485 Frequency Reference = 57.3 Hz

Field Name

Length

Range

Function Code

1 Byte

0x10

Starting Address

2 Bytes

0x0000 to 0xFFFF

Quantity of Registers

2 Bytes

1 to 123 (0x7B)

Field Name

Length

Range

Error Code

1 Byte

0x90

Exception Code

1 Byte

0x01 through 0x04

Request

Response

Field Name

(Hex)

Field Name

(Hex)

Function

10

Function

10

Starting Address Hi

00

Starting Address Hi

00

Starting Address Lo

26

Starting Address Lo

26

Quantity of Registers Hi

00

Quantity of Registers Hi

00

Quantity of Registers Lo

03

Quantity of Registers Lo

03

Byte Count

06

Registers Value Hi

00

Registers Value Lo

03

Registers Value Hi

00

Registers Value Lo

32

Registers Value hi

00

Registers Value Lo

96

Important: For bit descriptions, see Writing (06) Logic Command Data

in Appendix C of the PowerFlex 40 User Manual.

Error Responses

Table A Exception Code Table

If an attempt is made to write a sequence of parameters that includes
non-writeable parameters, the message will continue to write all writable
values, but will return an error code. If any of the parameters in the
sequence is read only, or run write inhibited, an error code of “4” will be
returned. If the value to be written is out of range or some other illegal
value, an error code of “3” will be returned. The returned error code does
not identify which of the parameters were not written.

Only a maximum of four control registers can be written beginning at
address 0x2000. If the starting address of the message is 0x2000 then the
length of the message must be 4 or less. If the starting register range and
the size of the intended write will reach beyond register 0x2003, an error
code of “2” will be returned and values will not be written to any of the
intended registers.

Request

Response

Field Name

(Hex)

Field Name

(Hex)

Function

10

Function

10

Starting Address Hi

20

Starting Address Hi

20

Starting Address Lo

00

Starting Address Lo

00

Quantity of Registers Hi

00

Quantity of Registers Hi

00

Quantity of Registers Lo

02

Quantity of Registers Lo

02

Byte Count

04

Registers Value hi

12

Registers Value Lo

34

Registers Value hi

02

Registers Value Lo

3D

Code

Meaning

1

Illegal Function Code: The function code received in the query message is not
available for the receiving device.

2

Illegal Data Address: The data address received in the query message is not
available for the receiving device.

3

Illegal Data Value: The data value received in the query message is not
available for the receiving device.

4

Service Failure: The receiving device is unable to perform the requested action.