beautypg.com

Rockwell Automation 20Y PowerFlex Active Front End in IP20 2500 Encl. Fr. 13 Left-Side Bus Splice Kit User Manual

Page 5

background image

Rockwell Automation Publication 20Y-IN005A-EN-P - October 2014

5

PowerFlex Active Front End in IP20 2500 MCC Style Enclosure Frame 13 Left-Side Bus Splice Kit

Step 5: Attach both enclosures using the air barrier panels and hardware in the

barrier kit (catalog number SK-Y1-MCCBARRIER), .

a.

Note the air barrier panel orientations in this figure, position the
barrier panels onto the left side of the AFE enclosure, and attach the
panels using the supplied hardware (see table below).

b. Attach the left side of the AFE enclosure to the right side of the

adjacent enclosure.
Torque fasteners to 55.0 in

•lb (6.2 N•M) when fastening the

enclosures together.

ATTENTION: The barrier kit must be used between the enclosures being
attached together to maintain proper air flow within each individual enclosure.
Failure to use the barrier kit can result in overheating that can cause equipment
damage.

SK-Y1-MCCBARRIER Kit Supplied Parts/Hardware

Part Number

Quantity

PowerFlex 755 High HP Cabinet Barrier Panel, Rear

PN-204975

1

Cabinet Barrier Panel, Upper

PN-160374

2

(1)

(1) Only one barrier panel is required.

Cabinet Barrier Panel, Lower

PN-160385

2

(1)

Screw, Hex Flange HD, Taptite, M6 x 20 mm

29171-640-02

22

PN-204975

Upper Air Barrier Panel
PN-160374

DC+ Bus

Location

DC– Bus
Location

Lower Air Barrier Panel
PN-160385

Barrier Panels on Left Side of AFE Enclosure