6.3 General Specifications
Operating Temperature Range
See Fig. 4.1 and Fig. 4.2
-25°C … +70°C (above +40°C load derating)
-13°F … +158°F (above +104°F load derating)
Cooling
Convection cooling; no internal fan
Storage Temperature Range
-25°C … +85°C
-13°F … +185°F
Load Derating above +40°C (104°F)
see Fig. 4.1
Humidity (non condensing)
95% rel H max.
Pollution Degree
2
Temperature Coefficient
0.02%/K
Reliability, calculated MTBF
in accordance to IEC 61709
CP T SNT 60W xx
CP T SNT 140W 12V 12A
CP T SNT 120W xx,
240W, xx 480W xx)
>1.8 Mio. hours
>1.2 Mio. hours
>0.9 Mio. hours
Switching Frequency
depending on Model
50 … 140kHz typ.
Remote ON/OFF
see Fig. 5.1, 5.2, 5.3 & 5.4 2 pin connector (see Fig. 3.1)
connect –S via a 1kΩ to –Vout Device off
Safety class
in accordance to IEC 536
Class 1
Case protection
in accordance to IEC 529
IP20
Isolation
See Safety Standards
-
Safety and Hazardous Location
Approvals
IEC SI-1729_B3
UL file E236157
UL file E255651
CSA file 246286
CSA file 246286
CSA file 246286
CSA file 246286
CE Mark
CB-Scheme as per IEC 60950-1
cULus Listed to UL508, CSA C22.2 No. 14
cRUus to ANSI/UL60950, CSA60950
CSA to C22.2 No. 107.1
cCSAus to CSA60950, ANSI/UL60950
cCSAus C1D2 to C22.2 No. 213, UL1604
cCSAus C1Z2 to CSA60079-15, UL60079-15 & ANSI/ISA 12.012.01
EN 60950-1, EN 50178, EN 61558-2-4
Electromagnetic compatibility
(EMC) Emissions
in accordance to the product family
standard Power Supply Industrial
Area
EN 61204-3
Conducted EMI on terminals
Radiated EMI
EN 55022 Class B, EN 55011 Class B, FCC Part 15-B
EN 55022 Class B, EN 55011 Class B, FCC Part 15-B
Input Current harmonics EN 61000-3-2 Class A
CP T SNT 70W 12V 6A and CP T SNT 90W 24V 3.8A up to full
output power
CP T SNT 140W 12V 12A and CP T SNT 180W 24V 7.5A up to 120
watt only
CP T SNT 360W 24V 15A up to 240 watt only
CP T SNT 600W 24V 25A up to 480 watt only
Flicker EN 61000-3-3
Electromagnetic compatibility
(EMC) Immunity
in accordance to the product family
standard Power Supply Industrial
Area
EN 61204-3
Standard
Level
Description
Perf. criteria
Electrostatic discharge (ESD)
Electrostatic discharge (ESD)
Radiated RF Fields [80 – 1000MHz]
Electrical fast transients / Bursts
Electrical fast transients / Bursts
Surge (Mains Supply)
Surge (Mains Supply)
Surge (Signal Supply)
Immunity to conducted radio frequency disturbances [0.15-80MHz]
Power frequency field immunity
Voltage Dips
Voltage sag immunity
IEC / EN 61000-4-2 ±4kV
Contact discharge
B
IEC / EN 61000-4-2 ±8kV
Air discharge
B
IEC / EN 61000-4-3 10V/m
B
IEC / EN 61000-4-4 ±2kV
Mains Supply
B
IEC / EN 61000-4-4 ±1kV
Signal Supply
B
IEC / EN 61000-4-5 ±1kV
between L & N
B
IEC / EN 61000-4-5 ±2kV
between L & PE and N & PE B
IEC / EN 61000-4-5 ±1kV
between ax & PE
B
IEC / EN 61000-4-6 10V
B
IEC / EN 61000-4-8 30A/m
B
IEC / EN 61000-4-11 70% UN / 40%/100% UN
B / C
SEMI F47
Environment
Vibration
Shock
IEC 60068-2-6
3 axis, sine sweep, 10 … 55Hz, 1g, 1oct/min.
IEC 60068-2-27
3 axis, 15g, half sine, 11ms
Enclosure Material
Aluminium (Chassis) / Zinc plated Steel (Cover)
Mounting
DIN-Rail mounting
Wall mounting
For DIN-Rails as per EN 50022-35 x 15 / 7.5
(snap-on self-locking spring)
With wall mounting bracket
Connection
Pluggable screw terminals (plugs included)