Weidmuller PRO-H Series Power Supplies User Manual
Page 7

Tel: (800) 849-9343
Fax: (804) 379-2593
www.weidmuller.com
Date:
28 September
2009
Issue: 1.0
Page
7
6. Technical Specifications
6.1 Input Specifications
* Input
voltage
max.
Output-
** Output
voltage
*** Output
current
Input current
at full load typ.
Inrush current
max. at +25°C (<2ms)
Efficiency
typ.
Model
range
power Factory Set ±1%
I
out max
115 VAC
230 VAC 115 VAC 230 VAC at 230VAC
CP T SNT 70W 12V
6A & CP T SNT
90W 24V 3.8A
100-240VAC
85-264VAC
(47-63 Hz)
78 Watt
90 Watt
12 VDC
24 VDC
6.5 A
3.75 A
2.0 A
2.1 A
1.0 A
1.0 A
12.0 A
20.0 A
82.0 %
85.0 %
CP T SNT 140W
12V 12A & CP T
SNT 180W 24V
7.5A, 48V 4A
100-120VAC/
220-230VAC
156 Watt
180 Watt
192 Watt
12 VDC
24 VDC
48 VDC
13.0 A
7.5 A
4.0 A
2.5 A
2.8 A
2.8 A
1.4 A
1.5 A
1.5 A
13.0 A
25.0 A
85.0 %
88.0 %
90.0 %
CP T SNT 360W
(24V 15A, 48V 7.5A)
85-132 VAC/
187-264 VAC
360 Watt
360 Watt
24 VDC
48 VDC
15.0 A
7.5 A
5.0 A
5.0 A
2.5 A
2.5 A
16.0 A
25.0 A
87.0 %
89.0 %
CP T SNT 600W
(24V 25A, 48V
12.5A)
(47-63 Hz)
Auto range
600 Watt
600 Watt
24 VDC
48 VDC
25.0 A
12.5 A
10.0 A
10.0 A
5.0 A
5.0 A
25.0 A
30.0 A
89.0 %
91.0 %
* Observe output current derating at operation below an input voltage of 110VAC (see Fig. 4.2).
** Output voltage adjustable 12 - 14VDC, 24 - 28VDC and 48 - 56VDC
*** Maximum current at nominal output voltage (Vout nom) and operating temperature up to +40°C max.
6.2 Output Specifications
Regulation
- Input Variation (Line Regulation)
- Load Variation (Load Regulation)
V
in min
- V
in max
10% - 100% of I
out max
0.5% max
0.5% max
2.0% in parallel operation
Output Voltage adjustable Range
with Potentiometer
12 V Model
24 V Model
48 V Model
12 - 14 VDC
24 - 28 VDC
48 - 56VDC
Ripple and Noise (20MHz Bandwidth) at V
in nom
und I
out max
200mV pk-pk max
Overload protection
Thermal protection
Automatic restart
Electronic Short Circuit Protection
Continuous
Constant current. Automatic restart
Parallel Operation
all Models; User selectable standard mode and
parallel mode by jumper on PCB
up to 5 Power Supplies possible
(Jumper position see Fig. 5.1, 5.2, 5.3 & 5.4)
Over Voltage Protection (OVP)
Trigger point at
20VDC 12VDC units
35VDC 24VDC units
60VDC 48VDC units
Hold-up Time
at full load and V
in
= 115VAC
at full load and V
in
= 230VAC
10ms min.
20ms min
Reverse Voltage Protection
(Power back immunity)
16VDC
35VDC
63VDC
Status Indicator (two colours)
Green LED
Red LED
Normal operation
Output failure – if AC input mains is present
Power Good Signal
Trigger threshold
12VDC units
24VDC units
48VDC units
Active output signals CP T SNT 70W 12V 6A
(referenced to –V
out
) CP T SNT 140W 12V 12A
CP T SNT 90W 24V 3.8A
24VDC units
48VDC units
Relay output DC-OK = Contact closed
9 – 11 VDC
18 – 22 VDC
36 - 44 VDC
11.0VDC ±1.0VDC / 20mA max.
11.0VDC ±1.0VDC / 40mA max.
22.0VDC ±2.0VDC / 10mA max.
22.0VDC ±2.0VDC / 20mA max.
44.0VDC ±4.0VDC / 15mA max.
30VDC / 1.0A max. for 12 / 24VDC models
48VDC / 0.5A max. for 48VDC models
Max. Capacitive Load
Unlimited