beautypg.com

Vicor DC MegaPAC DC-DC Switcher User Manual

Page 9

background image

Rev. 3/04

Vicor 800-735-6200 Mission Power Solutions (760) 631-6846 (phone) or (760) 631-6972 (fax)

Pg. 9

DC MegaPAC Operator’s Manual

General Shutdown /GSD (J10-5)

The GSD control pin on J10-5 allows simultaneous shutdown of all ConverterPAC outputs (see Connector Pin
Identification on page 14). This pin must be pulled down to less than 0.7V, and will sink 10 mA maximum to shut
down all outputs. The GSD pin should be open circuited or allowed to exceed 4.5V when not in use, or when the
outputs are to be enabled. Do not apply more than 6V to this input at any time. Normal open circuit voltage is 1.5
to 3V with respect to Signal Ground. If driven from an electromechanical switch or relay, a capacitor should be
connected to eliminate the effects of switch bounce.

Input Power OK (J10-18)
This is an active high TTL compatible signal and provides a status indication of the DC input power (see Table 2
and Connector Pin Identification on page 14). It is capable of sinking 20 mA maximum. This signal switches to a
TTL “1” when Vin is within its specified range.

Figure 9. Enable/Disable and General Shutdown

O

PERATING

R

ANGE

V

IN

OK T

RIGGER

Nominal

Low

High

Low Line

High Line

Code

Vdc

Line

Line

Cut Off

Cut Off

0

12 volts

10 volts

20 volts

6V to 10V

20V to 23V

1

24 volts

21 volts

32 volts

16V to 21V

32V to 36V

W

24W volts

18 volts

36 volts

12V to 18V

36V to 41V

2

36 volts

21 volts

56 volts

11V to 21V

56V to 63V

3

48 volts

42 volts

60 volts

34V to 42V

60V to 68V

N

48W volts

36 volts

76 volts

23V to 36V

76V to 86V

4

72 volts

55 volts

100 volts

40V to 55V

100V to 111V*

*Do not apply greater than 100 volts to the input of the DC MegaPAC.

Table 2. Input Voltage Range & Vin OK Limits

J10 INTERFACE CONNECTOR IDENTIFICATION
1 Signal Ground

14 No Connection

2 Signal Ground

15 Signal Ground

3 Overtemp. Warning

16 Vcc +5 volt, 300 mA

4 Analog Temperature

17 Vcc +5 volt, 300 mA

5 General Shutdown

18 Input Power OK

6 No Connection

19 Input Power Fail

7 No Connection

20 No Connection

8 Enable/Disable #8

21 Enable/Disable #7

9 Enable/Disable #6

22 Enable/Disable #5

10 Enable/Disable #4

23 Enable/Disable #3

11 Enable/Disable #2

24 Enable/Disable #1

12 Signal Ground

25 Gate Out Slot #8

13 Gate In Slot #1

Amp 25 pin connector #746862-2
plug for flat ribbon cable. Mates with
housing Amp #747548-2 plus slide
latch or similar.

2

3 4

5

6

7

1

8

9 10 11 12 13

14 15 16 17 18 19 20 21 22 23 24 25

Figure 8. Interface Connector