Vicor DC MegaPAC DC-DC Switcher User Manual
Page 15
![background image](/manuals/574918/15/background.png)
DC MegaPAC Operator’s Manual
Rev. 3/04
Vicor 800-735-6200 Mission Power Solutions (760) 631-6846 (phone) or (760) 631-6972 (fax)
Pg. 15
Specifications
Input Characteristics
Input Voltage
12 Vdc (10-20), 24 Vdc (18-36), 36 Vdc (21-56),
48 Vdc (36-76),
72 Vdc (55-100)
Power Factor
1.0
Line Regulation
0.2% max. from 10% to full load
Inrush Current
5A peak @ 48 Vdc input
Conducted EMI
BTR 2511
Issue 4
Transient Surge
EN/IEC 1000-4-2 Level 4
Output Characteristics
Load Regulation
0.2% max. from 10% to 100% load
0.5% max. from 0% to 10% load
Setpoint Accuracy
1% for standard voltages
2% for special or adjustable voltages
Ripple and Noise
Std. outputs: 2% or 100 mV p-p max., whichever is greater, 10% min. load
VXI options (
<
24V outputs): 50 mV p-p max for outputs
<
15 Vdc;
150 mV p-p max. for 24 Vdc outputs
QPAC, DualQPAC, JuniorPAC, RAMPAC: <10mV p-p max.
Overcurrent Protection
105-130% > 5V outputs & DualPACs, JuniorPACs, RAMPACs, DualQPACS,
JuniorQPACs
30-125%
<
5V outputs
Overvoltage Protection
ModuPACs and QPACs: 115-135%
N/A to DualPACs, JuniorPACs, BatPACs, RAMPACs, DualQPACs and
JuniorQPACs
Efficiency
83% typical
Output Power
1600W @ 45°C (Output power dependent upon Input voltage)
Environmental Characteristics
Storage Temperature
-40°C to +65
°C
Operating Temperature
C-grade: 0
°C to +45°C full power, 0°C to +65°C half power
I-grade: -20
°C to +45°C, -20°C to +65°C half power
See temperature derating curves.
Safety Approvals
UL 1950 (2nd), CSA C22.2 No. 234, IEC 950, EN 60 950
Product Weights
9.25 lbs (4,2 kg) fully configured
0.7 s (0,32 kg) ConverterPAC
Warranty
1 year
Humidity
0-95% noncondensing
Altitude