Thrush DSVE Series User Manual
Page 20

Thrush Co.
Manual #9636-0550
4.5 Operation
The Thrush HOT-PAK is an indirect fired semi-instantaneous water heater. It utilizes a
shell and tube heat exchanger and industry standard controls to provide a constant
source of hot water for an open system. Figures 4-6, 4-7 and 4-8 show the Hot-Pak in
various stages of the operation sequence. A standard Hot-Pak is shown, actual
configuration may vary.
To protect the tube bundle from damage, the unit must be filled with water before
allowing steam to enter.
With the unit full of water, and control panel set to the “ON” position, it will begin to
circulate the water inside the shell. Tubes and baffles are omitted for clarity. (Figure 4-6)
Figure 4-6 Operating Sequence (Circulated Water Flow)