RKI Instruments SD-705EC User Manual
Page 13

PT2E-1140
・For connection of terminal plate
<In case of direct connection>
Peel length of cable end:7 mm(3p terminal), 7mm(6p terminal)
※Do not make preliminary solder.
<In case of using the compressed ground terminal>
Bar terminal
: Model Al series(Maker : Phoenix Contact)
Terminal lug terminal
: Model CRIMPFOX UD6(Maker : Phoenix Contact)
・Torque for terminals
Torque:0.5∼0.6 Nm(3p terminal), 0.2∼0.25 Nm(6p terminal)
Applicable tool:Minus screw driver(Width below 3mm)
Be sure to use the exclusive use bar terminal. When used with other make
bar terminal than above, the function of this detector can not be warranted.
!
Caution
・
Cables
Power / Signal cable :CVVS 1.25∼2.0sq
Alarm relay contact cable :CVVS 1.25sq
During wiring work, take care not to damage the internal electric circuit.
!
Caution
・
Refer to 2−6 Wiring Method for connection of terminals.
Do not enter metals or other substances inside detector when opening the
detector lid.
Remove them inside detector to avoid the detector trouble or loss of ability for
explosion proof.
WARNING
!
12