DCA-600SSV — GENERATOR SHUT-DOWN PROCEDURE

Normal Shutdown Procedure

To shutdown the generator use the following procedure:

1. Place both the GFCI and AUX circuit breakers as shown

in Figure 42 to the OFF position.

2. Place the engine speed switch (Figure 65) in the

LOW ” (down) position.

Figure 66. MPEC Control Switch (Off/Reset)

5. Press the

main circuit breaker “OFF” switch (Figure 40).

6. Verify that the

main circuit breaker “OFF” lamp (Figure 41)

is lit (ON).

7. Verify that the

all status LED on the MPEC display

are OFF (not lit).

8. Remove all loads from the generator.

9. Inspect entire generator for any damage or loosening of

components that may have occured during operation.

3. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

4. Place the

MPEC Control Switch (Figure 66) in the

OFF/RESET position.

Figure 65. Engine Speed Switch (Low)

NEVER stop the engine suddenly except in an emergency.

WARNING - SHUTTING DOWN THE GENERATOR

Emergency Shutdown Procedure

1. PUSH inward the emergency stop button located on the

engine operating panel (Figure 67) to turn off the
generator in the event of an emergency.

Figure 67. Emergency Stop Button

EMERGENCY

STOP

PUSH

TO STOP