PAGE 42 — DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09)

When starting generator in AUTO mode use the "

Manual

Start-up" procedure except where noted (see below).

1. Perform steps 1 through 4 in the

Before Starting section

(page 38) as outlined in the

Manual Starting Procedure.

Figure 63. Engine Speed Switch (High)

Figure 64. Off/Manual Auto Switch (AUTO)

4. Place the Off/Manual/Auto switch (Figure 64) on the

MPEC unit to the AUTO position.

NOTE

When the generator is set in the “
AUTO ” mode, the generator will

automatically start

in the event of

commercial power falling below a
prescribed level by means of a
contact closure that is generated
automatically by a transfer switch.

2. Set the

battery ON/OFF switch (Figure 62) to the “ON

position.

Figure 62. Battery ON/OFF Switch

3. Set the engine speed switch (Figure 63) to the “High

position.

5. Press the circuit breaker

ON Switch (Figure 58).

6. Verify that the circuit breaker on lamp (Figure 59) is lit.

7. Continue operating the generator as outlined in the

Manual Start-up procedure (start at step 10).

Before connecting this generator to any
building’s electrical system, a

licensed

electrician must install an isolation
(transfer)
switch. Serious damage to the
building’s electrical system may occur
without this transfer switch.

DANGER - ELECTRICAL SYSTEM HAZARDS

When running the generator in the AUTO mode, remember
the generator can start up at any time without warning.
NEVER attempt to perform any maintenance when the
generator is in the auto mode.

WARNING - AUTO MODE MAINTENANCE

When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator's
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.

CAUTION - BACKUP GENERATOR USE

The

Engine Speed Switch must be set to the "High"

position when running in the

Auto-Start mode. Failing to

set the switch in the proper position can result in damage
to your generator when it turns on.

CAUTION - ENGINE SPEED SWITCH

DCA-600SSV — GENERATOR START-UP PROCEDURE (AUTO MODE)

23. Observe the generator's ammeter (Figure 61) and verify

it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if a load is in use.

24. The generator will run until manually stopped or an

abnormal condition occurs.

Figure 61. Ammeter (Load)