beautypg.com

Dca-600ssv— generator start-up procedure (manual) – Multiquip DCA600SSV User Manual

Page 40

background image

PAGE 40 — DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09)

Figure 53. Voltage Adjust Control Knob

14. The generator's AC-voltmeter (Figure 52) will display the

generator’s output in VOLTS.

Figure 52. AC Voltmeter

Figure 51. Frequency Meter (Hz)

13. The generator's frequency meter (Figure 51) should be

displaying the 60 cycle output frequency in HERTZ.

7. Set the

battery ON/OFF switch (Figure 45) to the “ON

position.

Figure 45. Battery ON/OFF Switch

DCA-600SSV— GENERATOR START-UP PROCEDURE (MANUAL)

Figure 46. Pre-Heat Button/ Lamp

8. Press and hold the engine preheat button (Figure 46)

until the preheat lamp is lit (ON).

Pre-Heat

Lamp

Pre-Heat

Button

9. Place the engine speed switch in the “

LOW ” position

(Figure 47).

Figure 47. Engine Speed Switch (Low)

Figure 48. Auto-Off/Reset-Manual Switch

10. Place the Auto-Off/Reset-Manual switch in the “

Manual”

position to start the engine (Figure 48). Once the engine
starts, let the engine run for 1-2 minutes. Listen for any
abnormal noises.

11. Once the engine is warm and the engine is running

properly, place the engine speed switch in the “

HIGH

position (Figure 49).

Figure 49. Engine Speed Switch (High)

12.

Verify that the "Engine Running" status LED on the MPEC
unit (Figure 50) is "ON" (lit) after the engine has been started.

Figure 50. Engine Running LED (ON)

15. If the voltage is not within the specified tolerance, use

the voltage adjustment control knob (Figure 53) to
increase or decrease the desired voltage.