generatOr shUt-DOWn prOceDUres

When starting generator in

auTo mode use the “Manual

Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section

as outlined in the Manual Starting Procedure.

2. Place the

engine speed switch (Figure 52) in the

hIgh position

Figure 52. Engine Speed Switch (High)

3. Place the

mpeC Control Switch (Figure 53) in the

auTo position.

Figure 53. MPEC Control Switch (AUTO)

4. Continue operating the generator as outlined in the

Manual Start-up procedure (start at step 5).

normal ShuTDoWn proCeDure

To shutdown the generator, use the following procedure:
1. Place both the

maIn, gFCI and loaD circuit breakers

as shown in Figure 54 to the

oFF position..

Figure 54. Main, GFCI and Load

Circuit Breakers Off

WarnIng

never stop the engine suddenly except in an

emergency.

2. Place the engine speed switch (Figure 55) in the “LOW”

(down) position.

Figure 55. Engine Speed Switch (Low)

3. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

4. Place the

mpeC Control Switch (Figure 56) to the

oFF/reSeT position.

Figure 56. MPEC Control Switch (Off/Reset)

5. Verify that

all the status LEDs on the MPEC display

are

oFF (not lit).

6. Remove all loads from the generator.
7. Inspect entire generator for any damage or loosening

of components that may have occurred during

operation.

emergenCY ShuTDoWn proCeDure

1. To stop the engine in the event of an emergency,

puSh

the emergency stop button (Figure 57) inward. This

button is located on the engine operating panel, see

Figure 5.

Figure 57. Emergency Stop Button