page 34 — DCa180SSI/DCa180SSIu 60 hz gen. • operaTIon anD parTS manual — rev. #1 (08/02/10)

generatOr start-Up prOceDUre (ManUaL)

BeFore STarTIng

1. Place the

main, g.F.C.I., and aux. circuit breakers (Figure

36) in the oFF position prior to starting the engine.

Figure 36. Main, Aux. and GFCI

Circuit Breakers (OFF)

2. Make sure the

voltage change-over board has been

configured for the desired output voltage.

3. Connect the load to the

receptacles or the output

terminal lugs as shown in Figure 10. These load

connection points can be found on the output terminal

panel and the output terminal panel’s hard wire hookup

panel.

4. Tighten terminal nuts securely to prevent load wires

from slipping out.

5. Close all engine enclosure doors (Figure 37).

Figure 37. Engine Enclosure Doors

STarTIng (manual)

1. Place the engine speed switch (Figure 38) in the LOW

(down) position.

Figure 38. Engine Speed Switch (Low)

2. Place the

mpeC control switch in the manual

position to start the engine (Figure 39).

CauTIon

The engine’s exhaust contains harmful emissions.

alWaYS have adequate ventilation when operating.

Direct exhaust away from nearby personnel.

WarnIng

never manually start the engine with the main, gFCI

or auxiliary circuit breakers in the on (closed) position.

INCORRECT

CORRECT

Figure 39. MPEC Control Switch

(Manual Position)

3. Depending on the temperature of the coolant (cold

weather conditions), the pre-heat lamp (Figure 40) will

light (ON) and remain on until the pre-heating cycle has

been completed. After completion of the pre-heating

cycle, the light will go OFF and the engine will start up

automatically.

Figure 40. Pre-Heat Lamp

4. Once the engine starts, let the engine run for 1-2

minutes. Listen for any abnormal noises. If any

abnormalities exist, shut down the engine and correct

the problem. If the engine is running smoothly, place

the engine speed switch (Figure 41) in the

hIgh (up)

position.

Figure 41. Engine Speed Switch (High)

5. Verify that the

engine running status LED on the

MPEC module (Figgure 42) is lit (ON) after the engine

has started.

Figure 42. Engine Running LED (ON)

6. The generator’s frequency meter (Figure 43) should be

displaying the 60 cycle output frequency in

herTz.