Output terminal panel familiarization – Multiquip DCA180SSIU User Manual
Page 23
DCa180SSI/DCa180SSIu 60 hz gen/ • operaTIon anD parTS manual — rev. #1 (08/02/10) — page 23
OUtpUt terMinaL paneL faMiLiarizatiOn
120 vaC gFCI receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema
5-20R) receptacles provided on the output terminal panel.
These receptacles can be accessed in
any voltage
selector switch position. Each receptacle is protected by a
20 amp circuit breaker. These breakers are located directly
above the GFCI receptacles. Remember the load output
(current) of both GFCI receptacles is dependent on the
load requirements of the U, V, and W output terminal lugs.
Pressing the
reset button resets the GFCI receptacle after
being tripped. Pressing the
test button (See Figure 7) in
the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.
Figure 7. G.F.C.I. Receptacle
Twist lock Dual voltage 120/240 vaC receptacles
There are three 120/240V, 50 amp auxiliary twist-lock (CS-
6369) receptacles (Figure 8) provided on the output
terminal panel. These receptacles can be accessed
in any
voltage change-over board position.
Figure 8. 120/240V Twist-Lock Auxiliary
Receptacles
Each auxiliary receptacle is protected by a 50 amp circuit
breaker. These breakers are located directly above the
GFCI receptacles. Remember the load output (current) on
all three receptacles is dependent on the load requirements
of the
output Terminal lugs.
Turn the
voltage regulator control knob (Figure 9) on the
control panel to obtain the desired voltage. Turning the knob
clockwise will
increase the voltage, turning the knob
counter-clockwise will
decrease the voltage.
Figure 9. Voltage Regulator Control Knob
removing the plastic Face plate (hard Wire
hookup panel)
The
Output Terminal Lugs are protected by a plastic
face plate cover (Figure 10). Un-screw the securing bolts
and lift the plastic terminal cover to gain access to the
terminal enclosure.
After the load wires have been securely attached to the
terminal lugs, reinstall the plastic face plate.
Figure 10. Plastic Face Plate (Output Terminal