Generator start-up procedure (auto mode) – Multiquip DCA180SSIU User Manual
Page 36
page 36 — DCa180SSI/DCa180SSIu 60 hz gen. • operaTIon anD parTS manual — rev. #1 (08/02/10)
generatOr start-Up prOceDUre (aUtO MODe)
Figure 51. Ammeter (Load)
15. The generator will run until manually stopped or an
abnormal condition occurs.
STarTIng (auTo moDe)
Danger
Before connecting this generator to any
building’s electrical system, a
licensed
electrician must install an isolation
(transfer) switch. Serious damage to
the building’s electrical system may occur without this
transfer switch.
CauTIon
When connecting the generator to a isolation (transfer)
switch,
alWaYS have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
NOTICE
When the generator is set in the
auTo mode, the
generator will
automatically start in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
WarnIng
When running the generator in the
auTo mode,
remember the generator can start up at any time without
warning.
never attempt to perform any maintenance
when the generator is in the auto mode.
CauTIon
The engine speed switch
must be set to the “High”
position when running in the
auto-start mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
NOTICE
When the MPEC control switch is placed in the
auTo
position, the engine glow plugs will be warmed and the
engine will start automatically.