dca45SSIU4F 60 hz generator• operatIon manUal — rev. #0 (09/09/14) — page 35

normal ShUtdoWn procedUre

To shutdown the generator, use the following procedure:
1. Place both the

maIn, gFcI and load circuit breakers

as shown in Figure 47 to the

OFF position.

Figure 47. Main, Aux. and GFCI

Circuit Breakers (Normal OFF)

2. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

3. Place the

auto off/reset manual Switch (Figure 48)

in the

oFF/reSet position.

Figure 48.

auto off/reset manual

Switch

(Off/Reset)

4. Verify that all status LEDs on the ECU control panel

are

OFF (not lit).

5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of

components that may have occurred during operation.

emergencY ShUtdoWn procedUre

1. To shut-down the engine in the event of an emergency,

switch the

maIn, GFcI and load (Figure 49) circuit

breakers to

OFF position.

Figure 49. Main, Aux. and GFCI

Circuit Breakers (Emergency OFF)

aUtomatIc ShUt-doWn SYStem

This unit is equipped with safety devices to automatically

stop the engine in the event of low oil pressure, approximately

14 psi (97 kPa), or high water temperature, approximately

212° F (100° C), overspeed approximately +15%. The alarm

lamps on the ECU illuminate to signify the reason for the

shutdown.

NOTICE

Before inspecting generator, check that the Auto/

Manual Switch is in the

oFF/reSet position, and

place all circuit breakers in the

OFF position. Allow

sufficient time for adequate cooling. When ready to

restart, complete all steps in the Generator Startup

Procedure section of this manual.

GeNeratOr shUt-DOWN prOCeDUres