GeNeratOr start-Up prOCeDUre (MaNUaL MODe)

5. Use the voltage adjustment control knob (Figure 39)

to increase or decrease the desired voltage.

Figure 39. Voltage Adjust Control Knob

6. The ammeter (Figure 40) will indicate

zero amps with

no load applied. When a load is applied, the ammeter

will indicate the amount of current that the load is

drawing from the generator.

Figure 40. Ammeter (No Load)

7. The engine oil pressure gauge (Figure 41) will indicate

the oil pressure of the engine. Under normal operating

conditions the oil pressure is approximately 35 to 65

psi. (193~586 kPa).

Figure 41. Oil Pressure Gauge

8. The

coolant temperature gauge (Figure 42) will

indicate the coolant temperature. Under normal

operating conditions the coolant temperature should

be between 180°~225°F (75°~95°C) (

Green Zone).

Figure 42. Coolant Temperature Gauge

PSI

OIL PRESS

0

25

50

75

100

°F

WATER TEMP

100

140

180

220

260

9. The

tachometer gauge (Figure 43) will indicate the

speed of the engine when the generator is operating.

Under normal operating conditions this speed is

approximately 1800 RPM’s.

Figure 43. Engine Tachometer Gauge

10. Place the

main, gFcI, and aux. circuit breakers in the

ON position (Figure 44).

Figure 44. Main, Aux. and GFCI

Circuit Breakers (ON)

11. Observe the generator’s ammeter (Figure 45) and

verify it reads the anticipated amount of current with

respect to the load. The ammeter will only display a

current reading if a load is in use.

Figure 45. Ammeter (Load)

12. The generator will run until manually stopped or an

abnormal condition occurs.