beautypg.com

Maintenance – Multiquip GA-6HEB User Manual

Page 30

background image

pAgE 30 — ga6HB/ga6HeB 60 hz gENERATOR• OpERATiON ANd pARTs mANuAl — REv. #0 (03/13/14)

3. On the GFCI module (Figure 36), verify that the

green

POWER LED is

ON.

Figure 36. GFCI Module (Green LED ON)

4. Also verify that the AC voltmeter is registering a voltage

reading as indicated by Figure 41.

5. Next, press the

TEsT button on the GFCI module and

verify that the

green POWER LED turns OFF and the

red FAULT LED turns ON.

Figure 37. GFCI Module (Red/Fault LED ON)

6. Also verify that the main circuit breaker switch trips to

the

OFF position.

Figure 38. Circuit Breaker OFF (GFCI Test)

7. Verify that the AC voltmeter (Figure 39) on the

generator reads zero volts.

MANUAL RESET

P

O

W

E

R

F

A

U

L

T

GREEN

POWER

LED

MANUAL RESET

P

O

W

E

R

F

A

U

L

T

PRESS

RED

FAULT

LED

ON

OFF

mainTenanCe

Figure 39. AC Voltmeter (Zero Volts)

8. To restore power, press the RESET button (Figure 40)

on the GFCI module and verify that the

red FAULT LED

turns

OFF and the green POWER LED should turn ON

Figure 40. GFCI Module (Green LED ON Reset)

9. Verify that the AC voltmeter is registering a voltage

reading as indicated by Figure 41.

Figure 41. AC Voltmeter (120/240V)

120

240

V

MANUAL RESET

P

O

W

E

R

F

A

U

L

T

PRESS

GREEN

POWER

LED

120

240

V

NOTICE

It is recommended that the GFCI unit be tested when

the generator is initially taken out of the box. Then, the

generator should be tested daily at startup.

CAuTiON

The GFCI module is designed to interrupt power when

a ground fault exists to prevent injuries and shock

hazards.

dO NOT operate the generator if this test fails.

Consult a qualified electrician for repair or replacement

of the GFCI module.

This manual is related to the following products: