Standard test area enclosure operation, Hydraulic power off, Specimen installation and setup – MTS Landmark Floor Standing User Manual
Page 71
Description
Control/Indicator
Item
RJ-45, to Controller.
Connector
7
Shuts down the HPU.
Hydraulic Off
8
Starts the test action. Only if the application test software is active.
Start
9
Resets active interlock(s) providing the cause for the interlock(s)
has been remedied.
Interlock Reset
10
Press to enable the thumbwheel to position the actuator. Press
again to disable the thumbwheel. The indicator lights when the
thumbwheel is active.
Thumbwheel Enable
11
Indicator. When lit, indicates an active fault or interlock.
Fault
12
Used to enable/disable the handset. When the indicator is lit, the
handset is enabled for control of the actuator.
Handset Enable
13
Selects the highlighted line in the display.
Select (Enter)
14
Four lines, 20 characters per line.
Display
15
Standard Test Area Enclosure Operation
There are four operating modes for an MTS Landmark Test System:
•
Hydraulic Power Off
•
Specimen Installation and Setup
•
Run Mode
•
Service
Hydraulic Power Off
Hydraulic Power is prevented from energizing the circuit via the hydraulic service manifold. Full access to the
test area is allowed in this mode.
Specimen Installation and Setup
The controller provides a means for creating a specimen installation mode. This mode typically uses the
Channel Limited Channel (CLC) control method. The primary control channel is Displacement (stroke) with
maximum limits set on applied force. Tuning parameters unique to this mode optimize manual control during
this mode. In addition, a maximum velocity command is set.
The handset has the ability to have a configuration specific desired response to the thumbwheel encoder on
the handset for a precise level of control.
MTS Landmark™ Floor Standing Load Units Product Information 71
Operation