21 RG-TFMOD
Drive Control & Communication
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory Default
65 (41H)
15
Serial Link
01 - Disable
02 - 9600, 8, N, 2 with Timer
03 - 9600, 8, N, 2, without Timer
04 - 9600, 8, E, 1 with Timer
05 - 9600, 8, E, 1, without Timer
06 - 9600, 8, O, 1 with Timer
07 - 9600, 8, O, 1, without Timer
02 - 9600, N, 2 w/ Timer
67 (43H)
17
Rotation
01 - Forward Only
02 - Forward and Reverse
01 - Forward Only
68 (44H)
18
Motor Overload Type
01 - Speed Comp
02 - No Comp
01 - Speed Comp
69 (45H)
19
Acceleration Time
1 – 13000 (0.1 sec – 1300.0 sec)
200 (20.0 sec)
70 (46H)
20
Deceleration Time
1 – 13000 (0.1 sec – 1300.0 sec)
200 (20.0 sec)
71 (47H)
21
DC Brake Time
0 – 9999 (0.0 sec – 999.9 sec)
0 (0.0 sec)
72 (48H)
22
DC Brake Voltage
0 – 300 (0.0 - 30.0% of nominal voltage)
0 (0.0%)
73 (49H)
23
Minimum Frequency
0 – Max Frequency (0.0 – 240.0 Hz)
0 (0.0 Hz)
74 (4AH)
24
Maximum Frequency
Min Frequency – 2400 (0.0 – 240.0 Hz)
600 (60.0 Hz)
75 (4BH)
25
Current Limit
500 – 2000 (50 – 200%)
2000 (200%)
76 (4CH)
26
Motor Overload
300 – 1000 (30 – 100%)
1000 (100%)
77 (4DH)
27
Base Frequency
250 – 5000 (25.0 Hz – 500.0 Hz)
600 (60.0 Hz)
78 (4EH)
28
Fixed Boost
0 – 300 (0.0 – 30.0%)
10 (1.0%)
79 (4FH)
29
Accel Boost
0 – 200 (0.0 – 20.0%)
0 (0.0%)
80 (50H)
30
Slip Compensation
0 – 50 (0.0 – 5.0%)
0 (0.0%)
81 (51H)
31
Preset Speed #1
0 – Maximum Frequency (0.0 – 240.0 Hz)
0 (0.0 Hz)
82 (52H)
32
Preset Speed #2
0 – Maximum Frequency (0.0 – 240.0 Hz)
0 (0.0 Hz)
83 (53H)
33
Preset Speed #3
0 – Maximum Frequency (0.0 – 240.0 Hz)
0 (0.0 Hz)
84 (54H)
34
Preset Speed #4
0 – Maximum Frequency (0.0 – 240.0 Hz)
0 (0.0 Hz)
85 (55H)
35
Preset Speed #5 /
Skip Frequency #1
0 – Maximum Frequency (0.0 – 240.0 Hz)
0 (0.0 Hz)
86 (56H)
36
Preset Speed #6 /
Skip Frequency #1
0 – Maximum Frequency (0.0 – 240.0 Hz)
0 (0.0 Hz)
87 (57H)
37
Preset Speed #7 /
Skip Frequency #2
0 – Maximum Frequency (0.0 – 240.0 Hz)
0 (0.0 Hz)
88 (58H)
38
Skip Bandwidth
0 – 100 (0.0 - 10.0 Hz)
0 (0.0 Hz)
89 (59H)
39
Speed Scaling
0 – 65000 (0.0 - 6500.0)
0 (0.0)
90 (5AH)
40
Frequency Scaling
30 – 12000 (3.0 - 1200.0 Hz)
600 (60.0 Hz)
91 (5BH)
41
Load Scaling
100 – 2000 (10 – 200%)
2000 (200%)
92 (5CH)
42
Accel / Decel #2
1 – 13000 (0.1 sec – 1300.0 sec)
200 (20.0 sec)
1
= Drive's programming parameter number