Drive control & communication, 2 parameter list – Lenze TCF Series Drives Modbus Communications User Manual
Page 23

19 RG-TFMOD
Drive Control & Communication
6.2 Parameter List
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory Default
51 (33H)
01
Line Voltage
01 - High
02 - Low
01 - High
52 (34H)
02
Carrier Frequency
01 - 2 kHz
02 - 4 kHz
03 - 8 kHz
02 - 4 kHz
53 (35H)
03
Start Method
01 - Normal
02 - Start on Power-up
03 - Start w/DC Brake
04 - Auto Restart w/DC Brake
05 - Flying Restart 1
06 - Flying Restart 2
01 - Normal
54 (36H)
04
Stop Method
01 - Coast
02 - Coast with DC Brake
03 - Ramp
04 - Ramp with DC Brake
01 - Coast
55 (37H)
05
Standard Reference
Source
Speed Mode:
01 - Keypad
02 - Preset #1
03 - 0-10 VDC
04 - 4-20 mA
Torque Mode:
01 - Keypad
02 - Keypad
03 - 0-10 VDC
04 - 4-20 mA
01 - Keypad
56 (38H)
06
TB-14 OC Output
01 - None
02 - Run
03 - Fault
04 - Inverse Fault
05 - Fault Lockout
06 - At Set Speed
07 - Above Preset #3
08 - Current Limit
09 - Auto Speed (speed source via terminal strip)
10 - Reverse (rotation direction indication)
11 - Dynamic Braking
01 - None
57 (39H)
07
Bipolar Reference
01 - Disable
02 - Enable
01 - Disable
58 (3AH)
08
TB-30 Analog Output
01 - None
02 - 0-10 VDC Freq
03 - 2-10 VDC Freq
04 - 0-10 VDC %Load
05 - 2-10 VDC %Load
06 - 0-10 VDC Torque
07 - 2-10 VDC Torque
01 - None
1
= Drive's programming parameter number