6 lenze-specific parameters, 2 parameter l-c0142, Lenze-specific parameters – Lenze 2131IB User Manual
Page 45: Parameter l-c0142, Parameter setting

Parameter setting
6-22
BA2131EN
6.6
Lenze-specific parameters
6.6.1
Only 82XX: Lenze parameter Operating Mode (L-C0001)
Parameter
name
(Index)
Sub-I
ndex
Data
str.
Data
type
Meaning
(Initialization is printed in bold)
Operating
mode
(5FFE
hex
)
0
S
I32
Value
Control source
Setpoint source
Parameter source
0
Terminal
Terminal
PROFIBUS
1
Terminal
8201 (keypad)
PROFIBUS
2
Terminal
Terminal
PROFIBUS
3
PROFIBUS
PROFIBUS
PROFIBUS
6.6.2
Parameter L-C0142
This parameter L-C0142 prevents the drive from uncontrolled restarts after:
l
Mains connection and disconnection
l
Internal fault
l
Internal message (with pulse inhibit) > 0.5 s
If the controller sets the status “ Mesage“ because of an internal fault (e. g. short mains failure) and
the fault remains active longer than 0.5 s, the controller will be inhibited automatically.
The parameter L-C0142 has the following function:
l
L-C0142 = 1:
The controller restarts automatically as soon as the fault is not active any longer
l
L-C0142 = 0:
The controller remains inhibited and the drive cannot restart even if the fault is no longer
active.
– The drive restarts after a LOW-HIGH transition at one of the inputs for “ Controller inhibit“
(CHIN, e. g. at terminal X5/28)