2 parameter communication with the controller, Parameter communication with the controller, Parameter setting – Lenze 2131IB User Manual
Page 30

Parameter setting
6-7
BA2131EN
Fault messages in the error field (Data/Error)
Error class Error
code
Additional
code [hex]
Meaning
0
0
00
No fault
6
3
00
No access permission
6
5
10
Inadmissible job parameter
6
5
11
Invalid subindex
6
5
12
Data too long
6
7
00
The object does not exist
6
8
00
Data types are not identical
8
0
21
Cannot be executed because of local control
8
0
22
Cannot be executed because of unit status
8
0
30
Leave value range
8
0
40
Collision with other values
8
0
20
Service cannot be executed currently
6.3.2
Parameter communication with the controller
Read job
1. Determine the user data of the controller: i. e. determine the location of the DP user data in
the host.
2. Enter the address of the desired parameter in the field ” Index and subindex“ (DP output
data).
3. Job/service = Read job and the bit “ job/handshake“ must be changed (DP output data).
4. Check, whether the bit “ job/handshake“ is the same for the DP input data and the DP output
data. If the bit “ job/handshake“ is the same, the response has been received. You should
implement a time monitoring.
5. Check, whether the bit “ job/status“ is set. If the bit “ job/status“ is not set, the field
“ data/error“ contains the required parameter value. If the bit “ job/status“ is set, the reading
job is not executed properly and the field “ data/error“ contains an error information.
Write job
1. Determine the user-data range of the controller, i. e. determine the location of the DP
user-data in the host system.
2. Enter the address of the desired parameter in the field “ Index and subindex“ (DP output
data).
3. Enter the parameter value into the field Data/Error.
4. Job/Service = Write job and the bit job/handshake must be changed (DP output data).
5. Check, whether the bit “ job/handshake“ is the same for the DP input data and the DP output
data. If the bit “ job/handshake“ is the same, the response has been received. You should
implement a time monitoring.
6. Check, whether the bit “ job/status“ is set. If the bit “ job/status“ is not set, the job has not
been executed properly and the field “ data/error“ contains an error information. Otherwise,
the job has been executed without any faults.