Commissioning – Lenze E94AYCPM User Manual
Page 45
Commissioning
Possible settings via DIP switch
EDK94AYCPM DE/EN/FR/ES/IT 6.0
45
l
H1inbet−bevor
Example: setting the station address 23
DIP switch
64
32
16
8
4
2
1
Switch state
OFF
OFF
ON
OFF
ON
ON
ON
Value
0
0
16
0
4
2
1
Station address
= sum of all values = 16 + 4 + 2 + 1 = 23
)
Note!
Switch off the voltage supply of the communication module and then on again
in order to activate changed settings.
EMF2133IB compatibility mode
Establishing the software compatibility to the EMF2133IB communication module is
required for systems which communicate via an EMF2133IB communication module.
DIP switch 2133 serves to establish the software compatibility.
Switch
Switch state
Function
2133
ON
Establishing EMF2133IB compatibility
OFF
No EMF2133IB compatibility
)
Note!
ƒ
The PROFIdrive and DRIVECOM profiles are not supported. Only the
DRIVECOM parameter channel and the Lenze device control in the
"EMF2133IB" compatibility mode can be used.
ƒ
Switch off the voltage supply of the communication module and then on
again in order to activate changed settings.
,
EMF2133IB communication manual
Here you’ll find some detailed information on the EMF2133IB communication
module.