Commissioning

Possible settings via DIP switch

7

EDK94AYCPM DE/EN/FR/ES/IT 6.0

45

l

H1inbet−bevor

Example: setting the station address 23

DIP switch

64

32

16

8

4

2

1

Switch state

OFF

OFF

ON

OFF

ON

ON

ON

Value

0

0

16

0

4

2

1

Station address

= sum of all values = 16 + 4 + 2 + 1 = 23

)

Note!

Switch off the voltage supply of the communication module and then on again
in order to activate changed settings.

EMF2133IB compatibility mode

Establishing the software compatibility to the EMF2133IB communication module is
required for systems which communicate via an EMF2133IB communication module.

DIP switch 2133 serves to establish the software compatibility.

Switch

Switch state

Function

2133

ON

Establishing EMF2133IB compatibility

OFF

No EMF2133IB compatibility

)

Note!

ƒ

The PROFIdrive and DRIVECOM profiles are not supported. Only the
DRIVECOM parameter channel and the Lenze device control in the
"EMF2133IB" compatibility mode can be used.

ƒ

Switch off the voltage supply of the communication module and then on
again in order to activate changed settings.

,

EMF2133IB communication manual

Here you’ll find some detailed information on the EMF2133IB communication
module.