beautypg.com

7 commissioning, Possible settings via dip switch, Commissioning 44 – Lenze E94AYCPM User Manual

Page 44: 7commissioning

background image

7

Commissioning

Possible settings via DIP switch

EDK94AYCPM DE/EN/FR/ES/IT 6.0

44

l

H1inbet−bevor

7

Commissioning

Possible settings via DIP switch

E94YCPM001D

The front panel DIP switches can be used to set
ƒ the station address (switches 1 ... 64)
ƒ compatibility with the EMF2133IB communication module (switch 2133)

Setting the station address

ƒ The station addresses for several interconnected PROFIBUS nodes have to differ from

each other.

ƒ Valid address range: 1 … 126 (max. 125 slave nodes)
ƒ The station address can be set via DIP switches 1 ... 64, or using the »Engineer« (code

C13899 / C14899).

Specification of the station address via ...

DIP switch

C13899 / C14899

Condition

At least one switch 1 … 64 = ON

All switches 1 ... 64 = OFF (Lenze
standard setting)

All switches 1 ... 64 = ON (invalid
value "127")

The labelling of the housing corresponds to the values of the individual DIP switches for
defining the station address.