4 electrical installation, Important notes, Electrical installation – Lenze E94AZHB0101 User Manual
Page 38: 4electrical installation
4
Electrical installation
Important notes
EDKE94AZHB DE/EN/FR/ES/IT 1.0
38
l
H1_E_INST−−−−(DUMMYSEITEVOR)−−−
4
Electrical installation
Important notes
,
During installation the notes given in the documentation for the standard
device must be observed!
(
Stop!
Requirements concerning the brake cable (connection BD1/BD2):
ƒ
The brake cables must be shielded if they are incorporated in the motor
cable.
– Operation with unshielded brake cables can destroy the motor brake
control.
– We recommend the use of Lenze system cables (motor cable with
separately shielded additional cores).
ƒ
When using a permanent magnet holding brake, ensure the correct
polarity of the brake cable.
– If the terminals are reversed, the brake does not release. Since the motor
runs against the closed brake, the brake can be destroyed.
ƒ
Connect the shield on both sides of PE.
Requirements concerning the supply voltage U
DC
(connection +/−):
ƒ
The motor brake control must always be supplied with a separate 24 V
supply.
– A common supply of the motor brake control and the control card of the
controller is not permissible since otherwise the double insulation
between both components would be reduced.
ƒ
Set U
DC
so that the operating voltage of the brake is within the admissible
range and the maximum supply voltage of the motor brake control will not
be exceeded.