Commissioning 9 programming parameters – Lenze SMVector RS-485 LECOM User Manual
Page 25

23
CMVLC401A
Commissioning
9
Programming Parameters
There is an offset of 1000 between the Drive Programming Parameter numbers and the code numbers used in the
LECOM messages. For example, if you want to read Drive Programming Parameter P103 (Maximum Frequency) over
the LECOM network, you would read code number 1103.
9.1
Fault History (P500)
Value
Display Fault Message
0
No Fault
1
TMP Output Fault
2
F.OF
Output (Transistor) Fault
3
F.OF1 Ground Fault
4
F.AF
High Drive Temperature
5
F.rF
Flying Start Fault
6
F.HF
High DC Bus Voltage
7
F.LF
Low DC Bus Voltage
8
F.PF
Motor Thermal Overload
9
F.GF
OEM Fault
10
F.IL
Illegal Setup
11
F.dbF Dynamic Brake Over Temperature
12
F.SF
Single Phase Fault
13
F.EF
External Fault
14
F.CF
Control Fault
15
F.UF
Start Error (Power loss)
16
F.cF
Incompatibility Fault
17
F.F1
Internal Fault 1 (EPM)
18
F.F2
Internal Fault 2
19
F.F3
Internal Fault 3
20
F.F5
Internal Fault 5 (stack overflow)
21
F.F5
Internal Fault 5 (stack underflow)
22
F.F6
Internal Fault 6
23
F.F7
Internal Fault 7
24
F.F8
Internal Fault 8
25
F.F9
Internal Fault 9
26
F.bF
Personality Fault
27
F.F12 Internal Fault (AD Offset)
28
F.JF
Internal Fault (Remote Keypad Lost)
29
F.AL
Assertion Level switched during Operation Fault
30
F.F4
Internal Fault 4 (FGD Missing)
31
F.F0
Internal Fault 0 (PW Missing)
32
F.FoL Follower Lost
33
F.F11 ISO Comm Fault
34
F.ntF Internal Fault (Module Communication (SPI) Timeout)
35
F.Fnr Internal Fault (FNR: Invalid Message Received)
36
F.nF1 Network Time-out