Commissioning – Lenze SMVector RS-485 LECOM User Manual

Page 24

background image

22

CMVLC401A

Commissioning

Code
Number

Parameter Name

Default Range of Adjustment

Important

C0200

Software
Identification

Software identification string:
example “33SSSMD-M_14000”
LECOM Format = VS

Read only

C0201

Software
Generation Date

Software generation date:
example “2008-10-18”
LECOM Format = VS

Read only

C1050

Network Controlled
Digital Output
(TB14) + Relay

0 = de-energized
1 = energized
bit 9:

TB-14 state

bit 10: Relay state
other bits are not used

Refer to section 8.1.1

C1055

Network Controlled
Analog Output

0.0%

0.0

100.0

Refer to section 8.1.2

C1060

Keypad Speed
Command

20.0 Hz P102

P103

C1061

Network Speed
Command

0.0 Hz P102

P103

C1070

Keypad PID
Setpoint Command

0.0

-99.9

3100.0

Read only

C1071

Network PID
Setpoint Command

0.0

-99.9

3100.0

Read-only

C1072

Actual PID setpoint

0.0

-99.9

3100.0

Read only

C1073

PID Setpoint
Command

0.0

-99.9

3100.0

Read only

C1074

PID Feedback

0.0

-99.9

3100.0

Read only

C1080

Keypad Torque
Command

100% 0.0

400.0

C1081

Network Torque
Command

0%

0.0

400.0

C1099

Parameter Version

Refer to section 8.1.3

8.1.1 C1050 (Network Controlled Digital Output)

To control the state of the relay or digital output (TB14), Drive Programming Parameter P140 and/or P142 must be set
to 25 (Network Controlled).

8.1.2 C1055 (Network Controlled Analog Output)

To control the state of the analog output (TB30), Drive Programming Parameter P150 must be set to 09 (Network
Controlled).

8.1.3 C1099 (Parameter Version)

The Parameter Version identifies the parameter set for the current version of software. If the Parameter version is
different between two drives, it could indicate that a register has been added or deleted, a register’s min/max limits
have changed, a register’s function has been changed, or a register’s default value has been changed.