Commissioning – Lenze SMVector RS-485 LECOM User Manual
Page 24
22
CMVLC401A
Commissioning
Code
Number
Parameter Name
Default Range of Adjustment
Important
C0200
Software
Identification
Software identification string:
example “33SSSMD-M_14000”
LECOM Format = VS
Read only
C0201
Software
Generation Date
Software generation date:
example “2008-10-18”
LECOM Format = VS
Read only
C1050
Network Controlled
Digital Output
(TB14) + Relay
0 = de-energized
1 = energized
bit 9:
TB-14 state
bit 10: Relay state
other bits are not used
Refer to section 8.1.1
C1055
Network Controlled
Analog Output
0.0%
0.0
…
100.0
Refer to section 8.1.2
C1060
Keypad Speed
Command
20.0 Hz P102
…
P103
C1061
Network Speed
Command
0.0 Hz P102
…
P103
C1070
Keypad PID
Setpoint Command
0.0
-99.9
…
3100.0
Read only
C1071
Network PID
Setpoint Command
0.0
-99.9
…
3100.0
Read-only
C1072
Actual PID setpoint
0.0
-99.9
…
3100.0
Read only
C1073
PID Setpoint
Command
0.0
-99.9
…
3100.0
Read only
C1074
PID Feedback
0.0
-99.9
…
3100.0
Read only
C1080
Keypad Torque
Command
100% 0.0
…
400.0
C1081
Network Torque
Command
0%
0.0
…
400.0
C1099
Parameter Version
Refer to section 8.1.3
8.1.1 C1050 (Network Controlled Digital Output)
To control the state of the relay or digital output (TB14), Drive Programming Parameter P140 and/or P142 must be set
to 25 (Network Controlled).
8.1.2 C1055 (Network Controlled Analog Output)
To control the state of the analog output (TB30), Drive Programming Parameter P150 must be set to 09 (Network
Controlled).
8.1.3 C1099 (Parameter Version)
The Parameter Version identifies the parameter set for the current version of software. If the Parameter version is
different between two drives, it could indicate that a register has been added or deleted, a register’s min/max limits
have changed, a register’s function has been changed, or a register’s default value has been changed.