Lenze SMVector RS-485 LECOM User Manual
Page 10

8
CMVLC401A
Commissioning
4
Parameters for use with RS-485/LECOM
4.1
Drive Communication Parameters
The parameters listed in Table 5 are always present on the drive, even if there is no communication module installed.
Table 5: Drive Communication Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P400
Network Protocol
0 Not Active
1 Remote Keypad
2 Modbus RTU
7 LECOM-B
P401
Module Revision
01.0.0 Display reads 01.x.x where:
01 = RS485/Remote Keypad Module
x.x = Module Revision
Read only
P402
Module Status
0
0 Not Initialized
Read only
1 Initialization: Module to EPM
2 Initialization: EPM to Module
3 Online
the communications between the drive
and module are working properly.
4 Failed Initialization Error
5 Time-out Error
6 Initialization Failed
Module type mismatch ( 0 )
7 Initialization Error
Protocol Selection mismatch ( 0 )
P403
Module Reset
0
0 No Action
1 Reset Module parameter values to
default.
Returns module parameters 401…499 to
the default values shown in this manual.
P404
Module Time-out
Action
3
0 Ignore
• Action to be taken in the event of an
SPI Time-out.
• SPI Time-out is fixed at 200ms.
1 STOP (refer to 11 )
2 Quick Stop
3 Fault ( n )
P405
Network Fault
0
0 No Fault
Read only, see P425 and P426
1 Network Time-out, F
P406
Proprietary
Module specific
Read only
NOTE:
If this parameter returns a value of 16, the software version in this SMVector drive
does not support the LECOM functionality. Contact factory technical support.
P498
Missed Messages
Drive to Module
Read only
P499
Missed Messages
Module to Drive
Read only