Drive control & communication, Programming parameters – Lenze smd Series Drives User Manual
Page 23

19 RG-SDMOD
Drive Control & Communication
6
smd
Programming Parameters
6.1 Format
NOTE - Attention
Parameter list presented in Section 6.2 is valid only for
smd parameter version 400 and
507. For revisions, refer to appropriate
smd Manual.
Abbreviations:
SA
(1byte) Drive Address (1-247)
RA
(1byte) Register Address
CRCH Cyclic Redundancy Check High byte
CRCL Cyclic Redundancy Check Low byte
READING:
Message structure for reading 1 word: (most of parameters)
Request: SA 03 00 RA 00 01 CRCH CRCL
Response:
SA 03 02 DH DL CRCH CRCL
Message structure for reading 4 word: (Parameter C99 Software Version)
Request: SA 03 00 RA 00 04 CRCH
CRCL
Response: SA 03 08 D1H D1L D2H D2L D3H D3L D4H D4L CRCH CRCL
WRITING:
Message structure for writing 1 word: (all parameters)
Request: SA 06 00 RA DH DL CRCH CRCL
Response:
SA 06 00 RA DH DL CRCH CRCL
LEGEND for Parameter List
1st Column:
Parameter No.
1
= Drive's programming code number
4th Column:
Range of Adjustment
2
= Selections in bold are for
smd models with PV507 only.