beautypg.com

6 electrical installation, Important notes, Electrical installation – Lenze E84AZESR RFI filter 3-29A User Manual

Page 56: 6electrical installation

background image

6

Electrical installation

Important notes

EDK84AZESRx DE/EN/FR/ES/IT 2.0

56

l

H1_E_INST−−−−(DUMMYSEITEVOR)−−−

6

Electrical installation

Important notes

{

Danger!

Dangerous electrical voltage

All power terminals remain live for up to three minutes after mains
disconnection.

Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes before
working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

{

Danger!

Hazardous electrical voltage

For the variants E84AZESxxxxxSDand E84AZESxxxxxLD the discharge current
to PE is > 3.5 mA AC or > 10 mA DC.

Possible consequences:

ƒ

Death or severe injuries when touching the device in case of a fault.

Protective measures:

ƒ

Implement the measures required in EN 61800−5−1, especially:
– Fixed installation
– The PE connection must comply with the standards (PE conductor

diameter

³ 10 mm

2

or use a double PE conductor)