JUMO 707030 dTRANS T03 2-Wire/3-Wire Transmitter Data Sheet User Manual
Page 4
2013-07-31/00391028
Data Sheet 707030
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Page 4/10
Technical data for 3-wire transmitter
(Types 707033/..., and 707034/...)
Input for resistance thermometer
Measurement circuit monitoring to NAMUR recommendation NE43
Output
Supply voltage
dTRANS T03 BU
Type 707033/...
dTRANS T03 TU
Type 707034/...
Measurement input
Pt100 (EN 60751)
Range limits
-200 to +850°C
Connection circuit
2-wire or 3-wire circuit
Smallest span
25°C
Largest span
1050°C
Unit
measuring range configuration in °C or °F
Zero shift
for spans < 75°C fixed zero: -40°C, -20°C, 0°C, 20°C, 40°C
for span 75°C: ±50°C
for spans > 75°C: see “Range organization” on page 7
Sensor lead resistance
for 3-wire connection
11 per conductor
Sensor lead resistance
for 2-wire connection
factory-set: 0
lead resistance,
settable through setup program
Sensor current
0.5mA
Sampling rate
continuous measurement because of analog signal path
Underrange
0V
Overrange
rising to
11V to 14V (typically 12V)
Probe short-circuit
0V
Probe and lead break
positive: rising to
11V to 14V (typically 12V)
negative: 0V
Output signal
DC voltage 0 — 10V
Transfer characteristic
linear with temperature
Transfer accuracy
± 0.2%
a
a
All details refer to the range-end value 10 V
Damping of ripple
on supply voltage
> 40dB
Load
10k
Load error
± 0.1%
Settling time on a temperature change
10msec
Calibration conditions
24V DC at approx. 22°C
Calibration/configuration accuracy
± 0.2%
a, b, c
or
± 0.2°C
b
The larger value applies
c
If the measuring range end value > 600 °C then the calibration or configuration accuracy is
± 0.4 %
Supply voltage (Ub)
15 — 30V DC
Reverse polarity protection
yes
Supply voltage error
± 0.01% per V deviation from 24V
a
a
All details refer to the range-end value 10 V