Approvals/approval marks
Electrical data
Max. switching capacity
Selectable on the N/C contact (contact deck 1-2):
AC 400 V +10 %, 16 A
AC 230 V +10 %, 16 (2.5) A, cos
ϕ = 1 (0.6)*
AC 230 V +10 %, 25 (4) A, cos
ϕ = 1 (0.6)
DC 230 V +10 %, 0.25 A
Selectable on the N/O contact (contact deck 1-4):
TW, STW
STB
AC 400 V +10 %, 6.3 A
AC 230 V +10 %, 6.3 (2.5) A, cos
ϕ = 1 (0.6)*
AC 230 V +10 %, 2 (0.4) A, cos
ϕ = 1 (0.6)
DC 230 V +10 %, 0.25 A
AC 400 V +10 %, 2 A
AC 230 V +10 %, 2 (0.4) A, cos
ϕ = 1 (0.6)*
AC 230 V +10 %, 2 (0.4) A, cos
ϕ = 1 (0.6)
AC 230 V +10 %, 0.25 A
Snap-action switch, gold-plated AC / DC = 24 V, 0.1 mA
Min. switching capacity
To ensure the greatest possible switching reliability we recommend a minimum load of:
AC / DC = 24 V, 100 mA for silver contacts
AC / DC = 10 V, 5 mA for gold-plated contacts
* standard
Capillary and temperature probe
Type
Capillary
∅ 1.5 mm
Temperature probe
JUMO exTHERM-AT
Stainless steel (CrNi) 1.4571
Stainless steel (CrNi) 1.4571, welded
Capillary length
Max. 5000 mm
Capillary bending radius
≥ 5 mm
Control ranges and probe table
Control range
Max.
capillary length
Probe length "L"
For "d" = 4 mm
For "d" = 6 mm
TW
STW, STB
TW
STW, STB
Hysteresis
In °C
In mm
Approx. 2.5 %
Approx. 7 %
Approx. 2.5 %
Approx. 7 %
-20 to +50
5000
- -
- -
138
81
0 to +120
203
113
90
58
0 to +200
154
87
72
48
+130 to +190
- -
- -
115
70
+50 to +300
135
78
65
- -
+20 to +500
- -
- -
278
- -
+140 to +500
- -
- -
- -
126
Switching point tolerance in the middle section of the scale
Control range
in °C
TW
in K
STW upward adjustment
in K
STW downward adjustment
in K
STB
in K
-20 to +40
+2/-2
- -
- -
- -
-20 to +50
+3/-3
+0/-5
+5/-0
+0/-5
0 to +100
+5/-5
+0/-10
+10/-0
+0/-10
0 to +120
+5/-5
+0/-10
+10/-0
+0/-10
+130 to +190
+8/-8
+0/-16
+16/-0
+0/-16
0 to +200
+8/-8
+0/-16
+16/-0
+0/-16
+50 to +300
+12/-12
+0/-24
+24/-0
+0/-24
+20 to +500
+22/-22
- -
- -
- -
+140 to +500
+22/-22
+0/-44
+44/-0
+0/-44
Temperature monitors (TW) and safety temperature monitors (STW) are adjusted ascendingly in the middle section of the scale as standard
procedure. Safety temperature limiters (STB) are adjusted in the upper section of the scale. Special adjustments are possible upon request.
JUMO exTHERM-AT
Switching function
Certificates/test confirmations
Tests
TW
EPS 11 ATEX 1 354
ATEX
STW
IECEx EPS 13.0046
IECEx
TZ 372
STB
POCC DE.ME92.B02680
GOST