beautypg.com

6 instrument description – JUMO 602021 Panel-Mounted Thermostat EM Series Up to 500C Operating Manual User Manual

Page 25

background image

25

6 Instrument description

Switching point
accuracy

(in % of scale span; referred to setpoint or limit value
at T

A

+22 °C, with rising temperature)

Protection

EN 60 529 - IP00
Pollution degree 2

Operating
medium

water, oil, air, superheated steam

Time constant
t

0.632

Mode of
operation

as per EN 60 730-1, DIN EN 60 730-2-9 and DIN EN 14597

TR, TW

2 BL

TB

2 BFHLPV

STW(STB):

2 BKLNP

STB

2 BFHKLNPV

Explanation of codes:

2 mode of operation type 2

B automatic mode of operation with micro-disconnection

F can only be reset with tools

H free-release mechanism, contacts cannot be prevented from opening

K with probe break protection

L no auxiliary power required

P mode of operation type 2, verified through declared temperature cycling

V lockout

Type EM-...

Switching differential in %

Switching point accuracy in %

liquid-filled

gas-filled

in upper third of
scale or at limit

at start of scale

1

1 / 2.5

5
7

- -

3 / 5

6 / 10

± 1.5
± 3

,5

± 4

,5

± 4
± 5
± 6

2, 3

1 / 2.5

5
7

- -

3 / 5

6 / 10

+ 0 / - 3
+ 0 / - 6
+ 0 / - 8

+ 0 / - 5
+ 0 / - 8

+ 0 / - 10

4, 4/574,
5, 5/574

- -

- -

+0 / -5

+0 / -7

20, 30

7

10

+0 / -8

+ 0 / - 10

40, 40/574,
50, 50/574

- -

- -

in water

in oil

in air / superheated

steam

≤ 45 sec

≤ 60 sec

≤ 120 sec