2 receipt string – INFICON SKY CDGxxxD (RS232C) User Manual
Page 6
6
tira49e1-a (2010-02) RS232C.cp
The example is based on the following output string:
Byte
No.
0 1 2 3 4 5 6 7 8
Value 7 2 16 0 125 0 20 6 69
The instrument or controller (receiver) interprets this string as follows:
Byte No. Function
Value Comment
0 Length
of
datastring
7 (Set
value)
1
Page No.
2
CDG025D with output signal 10.24 V
2
Status
16
Pressure unit = Torr
3 Error
0
No
Error
4
5
Measurement
High byte
Low byte
125
0
Calculation of pressure value: Conversion
formula
→ 4
6
Read command
20
Software version = 20 / 20 = 1.0
7
Sensor type
6
F.S.R.= 10
+3
8
Check sum
169
2 + 16 + 0 + 125 + 0 + 20 + 6 =
169
dec
≙
00 A9
hex
High order byte is ignored
⇒
Check sum = A9
hex
≙
169
dec
Commands to the gauge are transmitted in receipt strings (frames) consisting of
five bytes (without
Byte No. Designation
Value
0
Data string length
3
(constant value)
1 Data
→ "Service command"
2 Data
→ "Address byte"
3 Data
→ "Data byte"
4 Checksum
of bytes No. 1 … 3
Low byte of checksum
1)
1)
Possible high bytes are ignored.
• The operation selected in byte No. 1 is addressed in byte No. 2.
• Variables are transmitted in byte No. 3. Variables >1 byte have to be
transmitted in several receipt strings (splitting).
Example
1.2 Receipt String
Structure of receipt string